Introduction 
 
Video Recorder - User Manual 
 
5
Table 1-1   Specifications (continued) 
Input Impedance 
51K 
5.6K 
Input Current 
0.9 mA @ 100 Vac 
1.1 mA @ 12 Vdc 
3.2 mA @ 24 Vdc 
Minimum ON Current 
0.3 mA 
0.3 mA 
Maximum OFF Current 
0.15 mA 
0.2 mA 
Base Power Required* 
50 mA maximum 
50 mA maximum 
OFF to ON Response 
5 to 30 ms 
1 to 8 ms 
ON to OFF Response 
10 to 50 ms 
1 to 8 ms 
Logic Inputs 
Number 
6 (dry contact) per module, up to 6 modules per video recorder 
Isolation from ground 
2300 Vac/1 min. 
Switching Voltage 
5 Vdc 
Switching Current 
5 mA 
Digital Outputs 
 
AC Outputs 
DC Outputs 
Number 
6 per module, up to 6 modules per video 
recorder. Only 1-5 on each module can 
be configured as DAT outputs. 
6 (current sinking) per module, up to 6 
modules per video recorder. Only 1-5 
on each module can be configured as 
DAT outputs. 
Operating Voltage 
15 to 264 Vac 
10.2 to 26.4 Vdc 
Output Type 
SSR (Triac) 
NPN open collector 
Peak Voltage 
264 Vac 
40 Vdc 
AC Frequency 
47 to 63 Hz 
N/A 
Isolation from ground 
2300 Vac/1 min. 
1100 Vac/1 min. 
Isolation between outputs 
350 Vac 
30 Vac 
ON Voltage Drop 
<1.5 Vac (>0.1A)  
<3.0 Vac (<0.1A) 
1.5 Vdc maximum 
Maximum Load Current 
0.5A per point 
0.3A per point 
Maximum Leakage Current 
4 mA (264 Vac, 60 Hz) 
1.2 mA (100 Vac, 60 Hz) 
0.9 mA (100 Vac, 50 Hz) 
0.1 mA @ 40 Vdc 
 
 
Maximum Inrush Current 
10A for 10 ms 
1A for 10 ms 
Minimum Load 
10 mA 
0.5 mA 
Base Power required* 
20 mA/ ON pt. 250 mA  
maximum 
120 mA maximum 
5V 
OFF to ON Response 
1 ms 
1 ms 
ON to OFF Response 
1 ms +1/2 cycle 
1 ms 
Fuses (European type 5 x 
20mm) 
1 per output, 1.0A slow blow 
1 per output 
1A fast blow 
Relay (Alarm) Outputs 
Number 
6 per module, up to 6 modules per video recorder. Only 1-5 on each module can be 
configured as DAT outputs. 
Contact Rating 
2A, 250 Vac on resistive load 
Isolation from ground 
2300 Vac/1 min. 
Isolation between outputs 
2300 Vac/1 min. 
Contact Type 
SPST normally open (NO), individually configurable to normally closed (NC) via 
jumper 
* Base Power Required is the power required to provided module operation within specifications.