Setpoint Profiler 
 
Video Recorder – User Manual 
 
178
5.2  Components of a profile  
Two PVs available 
Each profile can monitor up to 2 process variables.  The second PV is for monitoring a second variable 
related to your process.  The value of each PV is compared with the value of the profile.  If the 
difference between either PV and the profile value exceeds specified amounts, the profiler will Hold 
(soak), if enabled to do so. 
Number of segments 
Up to 63 segments may be in a profile. 
Time Units 
All segments use the same time base (seconds, minutes, or hours). 
4 types of ramp segments 
There are four ramp types selectable at the RAMP TYPE prompt. 
1. Value/Duration 
2. Time 
3. Rate 
4. External 
Value/Duration (Val/Dur)Ramp Type 
This is the only ramp type that allows consecutive ramps or soaks.  VALUE is the beginning value of the 
segment; TIME is the time needed to reach the VALUE of the next segment. 
Segment #1
Time
Segment #2
Time
Segment #3
Time
Segment #4
Time
Segments #1 & #2
Valu e
Segment #3
Value
Segments #4 & #5
 Value
Segment #5
Time
Time = time to reach next segment Value
Ramp Type = Value/Duration
Time = duration of soak
Value = value of soak
Value = beginning value of current segment
Features of this ramp type
* Allows consecutive ramps or soaks
* First segment can be a ramp or soak
Ramp segments
Soak segments
 
Figure 5-3   Value/Duration Ramp Type