Rate Ramp Type 
Each ramp segment’s TIME specifies the rate at which the profiler output will reach the next soak 
segment, where the rate is specified by the prompts TIME/TIME UNITS.  The ramp segment’s VALUE 
prompt is not used. 
Segment #1
Time
Segment #3
Time
Segment #1
 Value
Segment #3
Value
Ramp Type = Rate
              Example: Time = 3.  Time Units = Seconds.  PV units = degrees F.
              Therefore, profile will ramp to next soak Value at 3 degrees F per second
Value = not used with ramp segments
Value  = value of soak
Segment #2
Time = Rate
Features of this ramp type
* First and last segments must be soaks
* No consecutive ramps or soaks
Ramp segments
Time = rate at which next soak Value will be reached, in PV units/Time Units.
Soak segments
Time = duration of soak
 
Figure 5-5   Rate Ramp Type 
ATTENTION 
Rate ramp type’s TIME prompt is in engineering units of the PV, not in time units (seconds, minutes, or hours). 
 
External Ramp Type 
This ramp type works with the RAMP INCREMENT discrete input.  During a ramp segment, each time 
RAMP INCREMENT changes from OFF to ON, the profiler output incrementally changes by the amount 
specified in the ramp segment’s TIME (in units of the PV).  When RAMP INCREMENT changes from ON 
to OFF, the profiler output soaks at its present value.  This increment-soak repeats until the profiler 
output reaches the VALUE of the next soak segment.  The ramp segment’s VALUE prompt is not used.