Honeywell VRX180 Manuale Utente

Pagina di 294
Setpoint Profiler 
 
Video Recorder – User Manual 
 
181
Segment #1
Time
Segment #3
Time
Segment #1
 Value
Segment #3
Value
Value  = value of soak
Segment #2 Time
Segment #2 Time
Segment #2 Time
Segment #2
Elapsed time
Ramp Increment Off-to-On
 causes increme ntal value
 change toward next soak
 Value
Ramp Type = External
Features of this ramp type
* First and last segments must be soaks
* No consecutive ramps or soaks
Ramp segments
Soak segments
Time = amount profile will change toward next soak Value
when the Ramp Increment discrete switches on.
Value = not used with ramp segment.
Time = duration of soak
 Figure 5-6   External Ramp Type 
 
 
ATTENTION 
• 
External ramp type’s TIME prompt is in engineering units of the PV, not in time units (seconds, minutes, or 
hours). 
• 
To increment toward a lower soak value, enter a positive TIME amount.  The Setpoint Profiler “knows” to 
increment or decrement this amount toward the next soak value.