69-2076—01
Table 1. Recommended Ignition Cables.
Transformer Requirement:
Add current ratings of module, pilot valve, main valve, 
vent damper and any other components of the control 
system to determine transformer size requirement.
Approvals:
Varies with control model.
ANSI Z21.20 Automatic Gas Ignition Systems and 
Components.
ANSI Z21.23 Gas Appliance Thermostats.
EN298: Automatic Gas Burner Control Systems
ANSI Z21.87: Automatic Gas Shutoff Devices for Hot 
Water Supply Systems.
UL353 Limit Controls.
PLANNING THE INSTALLATION
Automatic Ignition Control domestic and commercial 
boiler systems are used on a wide variety of equipment. 
Some of these applications may make heavy demands on 
the controls, either because of frequent cycling, or 
because of moisture, corrosive chemicals, dust or 
excessive heat in the environment. In these situations, 
special steps may be required to prevent nuisance 
shutdowns and premature control failures. These 
applications require Honeywell Engineering review; 
contact your Honeywell Sales Representative for 
assistance.
Frequent Cycling
These controls are designed for use on domestic and 
commercial boiler systems that typically cycle less than 
10,000 cycles per year. In an application with significantly 
greater cycling rates, we recommend monthly checkout 
because the controls may wear out more quickly.
Water or Steam Cleaning
Once a module or gas control has been wet, it may 
operate unreliably and must be replaced. If the appliance 
is likely to be cleaned with water or steam, the controls 
and associated wiring should be covered so that water or 
steam cannot reach them. The controls should be high 
enough above the bottom of the cabinet so they will not 
be subjected to flooding or splashing during normal 
cleaning procedures. If necessary, shield the controls to 
protect them from splashing water. A NEMA 4 enclosure 
is recommended.
High Humidity or Dripping Water
Over time, dripping water or high ambient humidity can 
create unwanted electrical paths on the module circuit 
board, causing the module to fail. Never install an 
appliance where water can drip on the controls.
In addition, high ambient humidity can cause the control 
to corrode and finally fail.
Where the appliance may be installed in a humid 
atmosphere, make sure air circulation around the module 
and gas control is adequate to prevent condensation. It is 
also important to regularly check out the system. A NEMA 
4 enclosure may be needed.
Corrosive Chemicals
Corrosive chemicals can also attack the module and gas 
control and eventually cause a failure. Where chemicals 
may be used routinely for cleaning, make sure the 
cleaning solution cannot reach the controls. Where 
chemicals are likely to be suspended in the air, as in some 
industrial and agricultural applications, protect the module 
from exposure with a NEMA 4 enclosure.
Dust or Grease Accumulation
Heavy accumulation of dust or grease may cause the 
controls to malfunction. Where dust or grease may be a 
problem, provide covers for the module and gas control 
that limit environmental contamination. A NEMA 4 
enclosure is recommended for the module.
Heat
The controls can be damaged by excessively high 
temperatures. Make sure the maximum ambient 
temperature at the control locations will not exceed the 
rating of the control. If the appliance normally operates at 
very high temperatures, insulation, shielding, and air 
circulation may be necessary to protect the controls. 
Proper insulation or shielding should b provided by the 
appliance manufacturer; make sure adequate air 
circulation is maintained when the appliance is installed.
INSTALLATION AND CHECKOUT
When Installing This Product…
1. Read these instructions carefully. Failure to follow 
them could damage the product or cause a 
hazardous condition.
2. Check the ratings given in the instructions and on 
the product to make sure they are suitable for your 
application.
3. Installer must be a trained, experienced service 
technician.
4. After installation is complete, check out product 
operation as provided in these instructions.
Cable Type
Voltage 
Rating (rms)
Temperature Rating
°C
°F
UL Style 
3217
10,000
150
302
UL Style 
3257
10,000
250
484