S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS
69-2076—01
4
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death or property 
damage.
1. The module can malfunction if it gets wet, 
leading to accumulation of explosive gas.
• Never install where water can flood, drip or 
condense on module.
• Never try to use a module that has been 
wet—replace it.
2. Liquefied petroleum (LP) gas is heavier than air 
and will not vent upward naturally.
• Do not light pilot or operate electric switches, 
lights, or appliances until you are sure the 
appliance area is free of gas.
3. If a new gas control is to be installed, turn off 
gas supply before starting installation. Conduct 
Gas Leak Test according to gas control 
manufacturer instructions after the gas control 
is installed.
4. If module must be mounted near moisture or 
water, provide suitable waterproof enclosure.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property 
damage.
Disconnect power supply before beginning wiring 
to prevent electrical shock or equipment damage.
Perform Preinstallation Safety Inspection
The preinstallation checks described in ANSI Standard 
Z21.71 must be done before a replacement module is 
installed. If a condition which could result in unsafe 
operation is detected, the appliance should be shut off 
and the owner advised of the unsafe condition. Any 
potentially unsafe condition must be corrected before 
proceeding with the installation.
Maintenance Requirements in Severe 
Environments
Regular preventive maintenance is important in any 
application, but especially so in commercial, agricultural, 
and industrial applications, because:
1. In such applications, particularly commercial, the 
equipment can operate 100,000 to 200,000 cycles 
per year. Such heavy cycling can wear out the gas 
control in one to two years. A normal boiler applica-
tion, for which the controls were intended, typically 
operate fewer than 10,000 cycles per year.
2. Exposure to water, dirt, chemicals, and heat can 
damage the module or the gas control and shut 
down the control system. A NEMA 4 enclosure can 
reduce exposure to environmental contaminants.
The maintenance program should include regular 
checkout of the system as outlined under Checkout. 
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death or property 
damage.
Do not attempt to take the module apart or to 
clean it. Improper reassembly and cleaning may 
cause unreliable operation, leading to an 
accumulation of explosive gas.
Maintenance frequency must be determined individually 
for each application. Some considerations are:
Cycling frequency. Appliances that may cycle more than 
10,000 times annually should be checked monthly.
Intermittent use. Appliances that are used seasonally 
should be checked before shutdown and again before the 
next use.
Consequence of unexpected shutdown. Where the cost of 
an unexpected shutdown would be high, the system 
should be checked more often.
Dusty, wet, or corrosive environment. Since these 
environments can cause the controls to deteriorate more 
rapidly, the system should be checked more often.
Any control should be replaced if it does not perform 
properly on checkout or troubleshooting. In addition, 
replace any module if it is wet or looks like it ever has 
been wet. Protective enclosures as outlined under 
Planning the Installation are recommended regardless of 
checkout frequency.
Mount Module
Select a location close enough to the burner to allow a 
short (3 ft. [0.9 m] maximum), direct cable route to the 
igniter. Ambient temperature at the module must be within 
the range listed under Specifications. The module must 
be protected from water, moisture, corrosive chemicals 
and excessive dust and grease. Refer to Fig. 2 and 3 for 
recommended slot/hole pattern in appliance.
Fig. 2. Recommended slot/hole pattern in appliance 
(in mm).
100
M24198
16
16
55
4
99.5
4