Maintenance Object Repair Procedures 
9-1313
POWER 
9
lower left corner of the cabinet. Should anything go wrong with the battery or 
charger, they must be replaced using the procedure described in the ‘‘Replacing 
the Battery and Battery Charger’’ section below. The system will detect one of the 
following three problems with the batteries or charger:
Reserve Fault: the charger has detected a problem within itself or the 
batteries and has notified the system.
High Charge Rate: the batteries have been charging at a high charge rate 
for an excessively long period of time. This indicates that there is a short in 
the batteries or the charger.
Prepare to Disconnect (Low Battery): the batteries are in danger of being 
drained to a point where the batteries would be damaged. This warning 
often occurs after multiple power failures. 
The batteries take 30 hours to fully charge after being drained. A fully 
charged battery pack should bridge two power failures without causing a 
low battery warning to occur. 
Replacing the Battery and Battery Charger 
(J58890CE)
1. Move the power switch on the battery charger to OFF.
!
WARNING:
Always turn off the battery charger before replacing the batteries. 
Failure to do so will result in damage to the 397C battery charger.
2. Disconnect the cord from the outlet on the front of the battery charger.
3. Remove the screw at the top left of the cover and open the cover to 
access the charger.
4. Check the battery voltages at the test points. Check all 3 batteries wired in 
series (the voltage should be 144 volts, 3 X 48 volts = 144 volts) .
NOTE:
An ordinary voltmeter can be used to check battery voltages at the 
test points, but it may not produce valid results. If the battery voltage 
readings are below 48 volts (the voltages at test points should read 
144 volts, 3 x 48 volts = 144 volts), the battery is probably defective. 
However, a normal voltage reading does not necessarily mean the 
battery is good; under load, a defective battery with a normal 
reading on the voltmeter may discharge rapidly.
5. Check the battery dates and the preventive maintenance log. Replace the 
batteries if they are more than 2.5 years-old.