11.3  Battery Life and Replacement Procedure
The battery installed in the safety CPU module is used for data retention of the program 
memory and operation/error history during the power failure. Special relays SM51 and 
SM52 turn on due to the decrease of battery voltage. Even if the special relays turn on, the 
program and operation/error data are not erased immediately.
After relay SM51 turns on, replace the battery quickly within the data retention time for 
power failure (3 minutes).
POINT
SM51 turns on when the battery voltage falls below the specified value, and 
remains ON even after the voltage is recovered to the normal value.
SM52 turns on when the battery voltage falls below the specified value, and turns 
OFF when the voltage is recovered to the normal value.
After SM51 and/or SM52 turns on, replace the battery quickly.
SM51 and SM52 turn on when the battery voltage of the CPU module is lowered.
The battery voltage drop can be checked with the contents of the special registers SD51 
and SD52.
For details of SD51 and SD52, refer to Section 12.7.
Figure 11.1 Bit pattern
When the battery 
voltage is low, the 
value is  "1."
SD51, SD52
b15
b1 b0
to
Fixed at 0
Error of a CPU 
module battery