11
 - 6
11.3 Battery Life and Replacement Procedure
11.3.1 Battery lives of CPU modules
11
MAINTENANCE AND INSPECTION
11.3.1  Battery lives of CPU modules
 * 1: The power-on time ratio indicates the ratio of programmable controller power-on time to one day 
(24 hours).
(When the total power-on time is 12 hours and the total power-off time is 12 hours, the power-on 
time ratio is 50%.)
 * 2: The guaranteed value represents a battery life at 70
 , which is calculated based on the 
characteristic values of manufacturer-supplied memories (SRAM) and on the assumption of 
storage within the ambient temperature range of -40 to 75
 (operating ambient temperature of 0 
to 55
 ). 
 * 3: The actual service value (reference value) represents a battery life that is calculated based on the 
values measured at storage ambient temperature of 40
 . This value is intended for reference 
only, as it varies with characteristics of the memory.
 * 4: In the following status, the backup time after power OFF is 3 minutes.
•The battery connector is disconnected.
•The lead wire of the battery is broken.
Table11.3 Battery lives
CPU Module 
Type
Power-on Time 
Ratio
*1
Battery lives
Guaranteed 
value
*2
Actual service 
value (Reference 
value)
*3
After SM52 ON
(Backup time after 
alarm
*4
)
QS001CPU
0%
26,000hr
2.96 years
43,800hr
5.00 years
710hr
30 days
30%
37,142hr
4.23 years
43,800hr
5.00 years
710hr
30 days
50%
43,800hr
5.00 years
43,800hr
5.00 years
710hr
30 days
70%
43,800hr
5.00 years
43,800hr
5.00 years
710hr
30 days
100%
43,800hr
5.00 years
43,800hr
5.00 years
710hr
30 days