Humidity System, Cont’d
TROUBLE SHOOTING GUIDE
Problem
Possible Cause / Remedy
Compressor not running
• Loss of power to controller.
Check 110V supply and in-store
breaker.
• Loss of power to compressor.
Check for loose wires on controller
module.
No Humidity Plume
• Water turned off. Check main
water supply to regulator unit.
• Water tubing contacting ice/
frozen product. Thaw and insulate.
• Solenoid valve not opening.
Check 11OV power from control-
ler.
• Water pressure too low. Adjust
regulator while system is running.
• Tubing lines blocked or kinked.
Check and repair.
• Air pressure escaping. Check air
line for leaks (air pressure should
be 25 PSI).
• No water getting to nozzle.
Remove and clean orifice reducing
plate in regulator assembly.
Too much / Too Little
• Adjust controller settings. Shorten
“Mist On” time or increase “Mist
Off” time.
Moisture
• Adjust water pressure.