T8001F, T8024F FLUSH MOUNT PROGRAMMABLE THERMOSTAT
69-1465—3
4
Setting Fan Operation (Fuel) Switch 
(T8001F Only)
The fan operation (fuel) switch is preset at the factory in 
the F position. See Fig. 9. This is the correct setting for 
most systems. If this system is an electric heat system, 
set the switch to the E position. The E setting allows the 
fan to turn on immediately with the heating or cooling 
equipment in a system where the G terminal is 
connected.
Fig. 9. Fan operation (fuel) switch.
Mounting Thermostat to Wallplate
1. Slide SYSTEM switch to the Off position.
2. Slide the thermostat straight into the wallplate until 
it is flush against the wall. See Fig. 10.
Fig. 10. Mounting thermostat to wallplate.
INSTALLER SETUP 
Setting °F/°C Indication and Heat Cycle Rate
The following instructions provide the information 
necessary to change the heating cycle rate to match the 
heating equipment and to choose either Fahrenheit (°F) 
or Celsius (°C) display.
NOTE: All four steps must be completed to save 
changes to the °F/°C indication and the heat 
cycle rate.
1. Enter Installer Setup.
a. Use ▲ or ▼ keys to set the temperature set-
point to 52°F (11°C).
b. Press the ▲ and ▼ keys simultaneously for 
more than two seconds to enter installer setup.
c. When released, the three-digit software revi-
sion code is displayed.
d. Press the ▲ key. Factory configuration (FC) is 
displayed. (A typical example is shown, but 
information displayed varies by model. This 
information is for factory use only).
Optional System Checkout 
When in steps 1c and 1d only, pressing the ▼ key can be 
used to turn heat or cool outputs on and off. Change the 
SYSTEM switch setting to test heat or cool outputs. No 
action takes place If the system switch is in the Off 
position.
Examples:
System setting at HEAT: If heat is on, pressing 
the ▼ key turns it off; if heat is off, pressing the 
 key turns it on.
System setting at COOL: If cool is on, pressing 
the ▼ key turns it off; if cool is off, pressing the 
 key turns it on. The 5 minute minimum off 
time is bypassed.
NOTE: In installer setup only, each press of the ▲ key 
momentarily displays 1. Each press of the ▼ 
key momentarily displays 2. When the keys are 
released, these one-digit codes are no longer 
displayed. 
2. Setting °C or °F.
a. Press the ▲ key again to display the current 
setting.
b. Press the ▼ key to change the °C or °F indica-
tion.