T8001F, T8024F FLUSH MOUNT PROGRAMMABLE THERMOSTAT
5
69-1465—3
3. Setting Number of Cool/Heat Stages (T8024F 
Only).
a. Press ▲ to display number of cool stages.
b. Press ▼ to change number of cool stages.
c. Press ▲ to display number of heat stages.
d. Press ▼ to change number of heat stages.
4. Setting Heat Cycle Rate (see Table 2) for the cycle 
rate options and equipment.
a. Press the ▲ key to display the current heat 
cycle rate setting of 1,3, 4, 5, 6, 9, or 12 cph.
NOTE: If thermostat is set to operate two stages of heat 
(T8024 only), both stages operate at the 
selected cycle rate.
b. To change the heat cycle rate, press the ▼ key 
until your choice of 1, 3, 4, 5, 6, 9, or 12 is dis-
played. See Table 2.
c. Press the ▲ key to display control algorithm 
configuration default.
d. Press the ▲ key again to change control algo-
rithm to C1 or C3.
C1 = Standard control algorithm.
C3 = Aggressive control algorithm (can 
cause overshooting).
e. Press the ▲ key again. Current configuration 
(CC) is displayed. A typical example is shown, 
but CC varies by model. (This information is for 
factory use only.)
5. Exit Installer Setup. 
a. Press the ▲ key to save all changes and return 
to normal operation.
Table 2. Heating Cycle Rate
a
High efficiency furnace (90+).
b
Refer to the equipment manufacturer’s instructions.
M20216
M20215
M20217
M20218
M12589A
System
Cycles Per Hour
Steam, gravity
1
Hydronic heat, condensing gas 
furnaces
a
3
Gas or oil forced air
6
Electric heat
9
Special applications
b
4, 5, 12