T8601D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS
7
69-1410—2
a
Number 2 must be set to 1 to extend fan operation.
IMPORTANT
Review the settings to confirm that they match 
the system. Press Run Program to exit the 
Installer Setup. The thermostat has saved the 
Installer Setup changes and initiated a reset in 
order to operate using the new settings. Be sure 
to set the current day and time immediately.
Temperature 
range stops in 
heating
34
90
Highest heating setpoint 
setting.
40 to 89 Temperature range (1°F 
increments) of heating 
setpoint settings.
Temperature 
range stops in 
cooling
35
45
Lowest cooling setpoint 
setting.
46 to 99 Temperature range (1°F 
increments)  of cooling 
setpoint settings.
Not used
36
Temperature 
display 
adjustment
37
0
No difference in displayed 
temperature and actual 
room temperature
3 thru -3 1—Display adjusts to 1°F
higher than actual 
room temperature
2—Display adjusts to 2°F
higher than actual 
room temperature
3—Display adjusts to 3°F
higher than actual 
room temperature
-1—Display adjusts to
1°F lower than actual 
room temperature
-2—Display adjusts to
2°F lower than actual 
room temperature
-3—Display adjusts to
3°F lower than actual 
room temperature
Furnace air 
filter timer
43
2
30 days (System run time)
0, 1, 3, 4 0—off
1—10 days
3—60 days
4—120 days
(Time is counted when 
heat, cool or fan is 
running)
Humidifier pad 
monitor
44
0
Off
1, 2, 3 1—90 days
2—189 days
3—365 days
Ultraviolet (UV) 
air treatment 
system lamp 
monitor
45
0
Off
1
1—365 days
(Time is counted by 
calendar days in any 
mode.)
Table 3. Thermostat Installer Setup Options.
Select
Installer Setup 
Number 
(Press Time ! 
key to change)
Factory-Setting
Other Choices 
(Press ! or key to change)
Actual 
Setting
Display
Description
Display
Description