5
State
V
boost
V
float
14.4V
13.8V
PB-1000-12
28.8V
27.6V
57.6V
55.2V
PB-1000-24
PB-1000 -48
F igure 6.2 3 stag e ch arging curve
Constant
Current
60A
34.7A
17.4A
100%
10%
Ex planation for 3 stag es char ging curve
(0)Initial stage (bat tery ana lysis):
(1)Stage 1 (constant current):
(2)Stage 2 (constant voltag e):
(3)Stage 3 (Flo at voltage):
Check batte ry vo ltage le vel t o see if it is within the normal range, w hether o r no t
a ba ttery is c onn ecte d, o r if th e battery is alre ady full and f urth er c harg ing is no t
requ ired.
A constant current is provided so the battery can be quickly charged to 2.4V per cell.
A constant voltage of 2.4V per cel l is provided until the charging current naturally
A float voltage of 2.3V per cell is provided so that the battery can maintain full charge.
tapers down to 10% then move on to stage 3.
Charge Current
Start
Charge Voltage
boost
float
V
V
Constant Current
stage 1
stage 2
stage 3
Constant Voltage
Battery Full
Orange
Green
Color of LED
6.3 8 s tage charging (flick swi tch to "8" stage)
8 st age charging provides optimized charge t o lead acid battery. It also prolongs
bat tery life and increase storage cap acit y. Some of the ma in advantages are as
bel ow:
Advantage of pulse st age: Use pulse current to revi ve aged batt ery.
Advantage of recondit ion stage: Al low full charge of bat tery.

*For applications that u tilize the charger (PB-1000) t o charge bat teries and su pply.
System po wer simultaneously(e.g. UPS system), pl ease select "3 sta ge" chargin g
for the best use of the c har ger.