Meridian Data SecurStor iSCSI to SATA-II RAID Subsystem 16i ユーザーズマニュアル

ページ / 91
Appendix 
C
: Uninterruptible Power Supply
 
                
 
 C-3 
Step 5. Trigger the firmware to allow the subsystem to detect the UPS. 
To see how to do this please, refer to the Generic Operation 
Manual that came with the subsystem. 
 NOTE: 
• 
A UPS can be connected to the subsystem after the subsystem has 
been powered on, but you will have to trigger the firmware to allow 
the subsystem to detect the UPS. 
• 
If you are daisy chaining systems together, be sure to make all the 
cable connections and then power on the 
SecurStor 16i 
subsystem 
that is not directly connected to host computer before powering on the 
first subsystem. 
 
 
C.6   UPS Status Monitoring 
If a UPS has been correctly connected to the subsystem, the status of the UPS will be 
constantly monitored by the controller through the COM2 (audio jack) serial port. The status 
of the UPS will determine the controller’s write policy
,
 and messages that appear on the LCD 
panel and other monitoring devices will keep you informed of the UPS status. 
 
C.6.1 Normal Operational Status 
If the UPS has been connected to main power and the UPS battery power level is 
above 50%, then no status messages will appear and the default “Write Back” write 
policy will be implemented by the controller.
 
 
C.6.2 UPS Messages 
The following messages may appear on the LCD screen: 
Message 1: “UPS connection is absent” 
This message appears when COM2 has not been connected to the UPS. 
Message 2: “UPS connection detected” 
This message appears when the COM2 ports on the subsystem have been connected 
to the UPS. 
Message 3: “Warning: UPS AC Power-Loss detected” 
This message appears when the UPS battery power level remains above 50% but its 
connection to the AC power supply has been disrupted in some way. The write policy 
changes from write back to write through. 
Message 4:  “Warning: UPS Battery Low 50%. Please shut down to protect data 
loss” 
This message appears when the UPS battery power level has dipped below 50% of its 
capacity and the UPS has either been disconnected from the AC power supply or the 
AC power supply has been disrupted. The write policy will be changed from the