Adding and Deleting serial port access: 
Click on the Ports link in the Access column for the associated user.   
On the subsequent User Ports page, select or deselect ports to be accessed by the user and press Apply
FTP 
The FTP configuration page is used for setup and maintenance of all settings required to perform an 
FTP firmware upload.  See Appendix B: Uploading Firmware for more information on uploading 
firmware. 
Setting the FTP Host IP Address: 
Enter the IP address in the Host IP Address field and press Apply
Setting the FTP username: 
Enter the FTP server username in the Username field, and press Apply
Setting the FTP password: 
Enter the FTP server password in the Password field, and press Apply
Setting the filepath: 
Enter the path of the file to be uploaded in the Directory field, and press Apply
Setting the filename for upload: 
Enter the filename of the file to be uploaded in the Filename field, and press Apply
Testing the FTP upload configuration: 
This test validates that the unit is able to contact and log onto the specified FTP server, download the 
firmware file and verify that the firmware file is valid for this unit. 
Press Test.  
SNTP 
The SNTP configuration page is used for setup and maintenance of SNTP support. 
Setting the SNTP Server Address: 
Enter the IP address in the primary and/or secondary address field and press Apply
SNMP 
The SNMP configuration page is used for setup and maintenance of all settings required to enable 
SNMP support as well as access to the trap configuration pages.  For additional information on SNMP 
support and detailed descriptions of available traps, see SNMP on page 48. 
NOTE:  Traps are generated according to a hierarchical architecture; i.e. if a Tower Status enters a trap condition, only the 
Tower Status trap is generated.  Infeed and Outlet Status traps are suppressed until the Tower Status returns to Normal. 
Enabling or disabling SNMP support: 
Select Enabled or Disabled from the drop-down menu and press Apply
Setting the community strings: 
Enter the community string in the appropriate field and press Apply.  
Community strings may be 1 to 24 characters 
Setting the trap timer: 
Enter a trap timer value in the Error Trap Repeat Time field and press Apply
The Error Trap Repeat Time value may be 1 to 65535 (in seconds). 
Setting trap destinations: 
Enter an IP address in the appropriate Trap Destination field and press Apply
Enabling or disabling tower traps: 
Click on the Tower Traps link. 
On the subsequent Tower Traps page, select or deselect the desired traps and press Apply
18 
•   Operations 
Sentry PT22 
 
 
 