Sentry Industries PT22 ユーザーズマニュアル

ページ / 74
Load Trap 
The Load trap is generated whenever the total input load on an infeed exceeds a preset threshold.  Load 
traps include the reported input load, load status, Location of the Sentry, and identifier and name of the 
affected infeed. 
Any error state generates a Load trap and triggers the trap timer.  A new trap is generated at the end of 
every timer period until the Load returns to a non-error status. 
Load traps 
Status Error Description 
Normal 
 
Infeed is on and within preset thresholds 
NotOn 
 
Infeed is off 
Reading 
 
Non-error state – Load status currently being read 
LoadHigh 
Infeed current load exceeds preset threshold 
OverLoad 
Infeed current load exceeds the measurable range for the infeed 
ReadError 
Unable to read Load status 
NoComm 
x  
Communication to the infeed has been lost 
Configuring Traps 
SNMP Trap Command Summary  
Command Description 
Set Trap Tower Status 
Enables or disables the Tower Status trap 
Set Trap Infeed Status 
Enables or disables the Infeed Status trap off 
Set Trap Infeed Load 
Enables or disables the Infeed Load trap 
Set Trap Infeed HighThresh 
Sets the Infeed Load trap high limit 
Set Trap Outlet Change 
Enables or disables the Outlet Change trap 
Set Trap Outlet Status 
Enables or disables the Outlet Status trap 
Show Traps 
Displays trap configurations 
Enabling or Disabling a Status trap 
The Set Trap … Status command is used to enable or disable Status traps for a Tower, Infeed or Outlet. 
To Enable or Disable a Status trap: 
At the Sentry: prompt, type set trap (tower, infeed, or outletstatus, followed by the tower, infeed or 
outlet name, and on or off.  Press Enter, or 
Type set trap (tower, infeed, or outlet) status all, followed by on or off and press Enter
Examples 
The following command enables the Status trap for the first tower, using the tower’s absolute name: 
Sentry: set trap tower status .a on<Enter> 
The following command enables the Status trap for the tower named Florida_HQ_1: 
Sentry: set trap tower status Florida_HQ_1 on<Enter> 
NOTE:  Enabling lower hierarchical traps automatically enables traps of higher hierarchical value: i.e. enabling an Outlet 
Status trap automatically enables the Infeed and Tower Status traps for that outlet.  Conversely, if a Tower Status trap is 
disabled, all associated Infeed Status & Load and Outlet Status traps will be disabled. 
Sentry PT22 
Advanced Operations 
• 51 
Installation and Operations Manual