INSTALLATION
     WSK-24 WIRELESS OCCUPANCY SOLUTION 
3
62-0300ES—01
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow 
them could damage the product or cause a 
hazardous condition.
2. Check the ratings given in the instructions and on 
the product to make sure the product is suitable for 
your application.
3. Installer must be a trained and experienced service 
technician.
WARNING
Risk of electrical shock.
Can cause severe injury, property damage or 
death.
Disconnect power supply before installation and 
before servicing.
IMPORTANT
The thermostat may be a line voltage powered 
device. All wiring must comply with national and 
local electrical codes, ordinances and 
regulations.
The WSK-24 must be powered by an Approved 
24 Vac, Class 2, NEMA rated transformer.
Thermostat Configuration
Refer to the thermostat’s installation instructions for 
programming, mounting, and wiring the thermostat.
The receiver has a normally open dry contact relay. 
Therefore, the thermostat should be set so that the relay 
on the thermostat is normally closed.
Use Table 2 or Table 1 to determine the desired Installer 
Codes for the thermostat being used with the WSK-24.
Wiring
Prepare Thermostat for Receiver Wiring
Turn off the thermostat and remove the power source 
from the thermostat.
WARNING
Risk of electrical shock.
Can cause severe injury, property damage or 
death.
Disconnect power supply before servicing.
CAUTION
Equipment Damage Hazard.
Improper removal can damage the thermostat.
Carefully follow the thermostat removal directions.
Receiver and Thermostat Terminal Wiring
Table 1. MultiPRO™ Installer Setup Codes.
IS
Code
Code
Description
Option
Value
Option Description
0160
Schedule Options 0
Non-Programmable
0340
(Non-
program
mable)
Remote Temp 
Sensor/Remote 
Setback/
Changeover 
Input
5
Remote Setback
0341
Delay for Remote 
Setback
0
No Delay
2
Two Minute Delay
0342
Override Option
0
No Override during 
unoccupied
1
Override during 
unoccupied
0343
Unoccupied 
Heating Setpoint 
50-65 Range is 50 to 65°F 
(10 to 18°C)
0346
Unoccupied 
Cooling Setpoint
75-90 Range is 75 to 90°F 
(24 to 30°C)
Table 2. SuitePRO™ Installer Setup (IS) Codes.
IS
Code
Code 
Description
Option
Value
Option Description
19
Remote 
Setback
2
Hotel Card enabled N.C. with 
1 second software delay 
going from UnOccupied to 
Occupied; 
2 minute delay going from 
Occupied to UnOccupied.
4
Hotel Card enabled N.C. with 
1 second software delay 
going from UnOccupied to 
Occupied; 
30 minute delay going from 
Occupied to UnOccupied.
20
Remote 
Setback for 
Heating
50-70 Range is 50 to 70°F 
(10 to 21°C)
21
Remote 
Setback for 
Cooling
72-90 Range is 72 to 90°F
(22 to 32°C)
Table 3. Wiring Designations
Receiver
Harness
Wire
Typical
Thermostat
Terminals
Connection
Red
R
24 Vac Power
White
C
24 Vac Common
White/
Brown
Sc
Dry Contact; Normally 
Open
Brown
Sb
Dry Contact; Common