Therma-Stor Products Group Ultra-Aire 100V 사용자 설명서

다운로드
페이지 28
No dehumidification, compressor does not run but fan runs 
with fan switch and ventilation timer OFF and humidity control 
turned to ON.
1.Defective compressor run capacitor (Sec. 5.6).
2.Loose connection in compressor circuit (See Fig. 4).
3.Defective compressor overload (Sec. 5.6A).
4.Defective compressor (Sec. 5.6).
5.Defrost thermostat open (Sec. 5.8).
Fan runs with fan switch and ventilation timer OFF, but 
compressor cycles on & off.
1.Low ambient temperature and/or humidity causing unit to 
cycle through defrost mode.
2.Defective compressor overload (Sec. 5.6A).
3.Defective compressor (Sec. 5.6).
4.Defrost thermostat defective (Sec. 5.8).
5.Dirty air filter(s) or air flow restricted.
Fan does not run with fan switch in either position. Fan does 
not run with ventilation timer activated. Compressor runs 
briefly but cycles on & off with humidity control turned to ON.
1.Loose connection in fan circuit (See Fig. 4).
2.Obstruction prevents fan impeller rotation.
3.Defective fan.
4.Defective fan relay.
Fan runs with fan switch ON. Fan does not run with ventilation 
timer activated.
1.Defective ventilation timer.
2.Time not correct on ventilation timer.
3.Ventilation timer set to manual & switched OFF.
Evaporator coil frosted continuously, low dehumidifying 
capacity.
1.Defrost thermostat loose or defective (Sec. 5.8).
2.Low refrigerant charge
3.Dirty air filter(s) or air flow restricted.
4.Excessively restrictive ducting connected to unit.
Unit not providing ventilation. Ventilation timer notoperating 
correctly.
1.If timer is not functioning correctly, reset timer and reprogram 
(Sec. 3.5)
2.Check control wire connections (check connections at 
damper also)
3.Defective fresh air damper (Sec. 5.9)
7.4 Refrigerant Charging
If the refrigerant charge is lost due to service or a leak, a new 
charge must be accurately weighed in. If any of the old charge is 
left in the system, it must be recovered before weighing in the new 
charge. Refer to the unit nameplate for the correct charge weight 
and refrigerant type.
7.5 Fan Replacement
The centrifugal fan has a PSC motor and internal thermal overload 
protection. If defective, the complete assembly must be replaced.
1.Unplug the power cord.
2.If an outlet duct is connected to the unit, remove it.
3.Remove the cabinet side.
4.Remove the 3 screws attaching the electrical box
located in front of the fan to the base.
5.Disconnect the fan leads. Black from the fan relay and white 
from the run capacitor.
6.Pull the oil tubes out of the fan motor.
7.Remove the nuts & bolts holding the fan outlet flange to the 
cabinet end and remove the fan.
8.Reassemble the new fan by reversing the above procedure.
7.6 Compressor/Capacitor Replacement
This compressor is equipped with a two terminal external overload 
and a run capacitor, but no start capacitor or relay (See Figure 4).
CAUTION-ELECTRICAL SHOCK HAZARD: 
Electrical power must be present to perform 
some tests. These tests should be performed 
by a qualified service person.
7.6A Checking Compressor Motor Circuits
Perform the following tests if the fan runs but the compressor does 
not with the fan switch OFF and the humidity control ON.
1. Unplug the unit, remove the cabinet side and the electrical 
connection cover on the compressor top.
2.  Plug in the unit and turn the humidity control to ON. Check for 
110 volts from compressor terminal R to overload terminal 
3 using an AC voltmeter. If voltage is present, go to step 
3. If no voltage, there may be a loose connection in the 
compressor circuit. Test each component for continuity. See 
the appropriate section if a defect is suspected.
3.  Unplug the unit, then disconnect the red and yellow wires 
from compressor terminals R & S. Using an ohmmeter, check 
continuity between the points listed below.
4.  Compressor terminals C and S:  
No continuity indicates an open start winding. The 
compressor must be replaced. Normal start winding 
resistance is 3 to 7 ohms.
5.  Compressor terminals C and R: 
No continuity indicates an open run winding. The compressor 
must be replaced. Normal run winding resistance is .5 to 2 
ohms.
FOR HVAC INSTALLER AND HOMEOWNER
18
19
Ultra-Aire 100V Installer’s & Owner’s Manual
Ultra-Aire 100V Installer’s & Owner’s Manual