Connect a duct from outside to the 6" collar of the Ultra-Aire if you 
wish to provide fresh make-up air.
Crawlspace Installation: Locate a separate return for the Ultra-
Aire in a central area of the structure. Duct the supply of the 
Ultra-Aire to a 8" x 8" x 8" tee/damper that is 30% open to the 
crawlspace. Duct the other side of the tee to the air return of the 
existing HVAC system. If the existing HVAC system has a central 
return, duct the other side of the tee to the air supply of the existing 
HVAC system. Connect a duct from outside to the 6" collar of the 
Ultra-Aire if you wish to provide fresh make-up air. 
3.4E Installation in an Attic with an Existing Forced 
Air HVAC System
ALWAYS install a catch pan for condensate under the 
Ultra-Aire in an attic or condensate may drip down on 
the ceiling of the living space below.
Locate a separate return for the Ultra-Aire in a central area of the 
structure. Duct the supply of the Ultra-Aire to the air supply of the 
existing HVAC system. If the existing HVAC system has a central 
return, duct the supply of the Ultra-Aire to the air supply of the 
existing HVAC system. Connect a duct from outside to the 6" collar 
of the Ultra-Aire if you wish to provide fresh make-up air.
3.4F Installation in a Structure with Two Forced Air 
HVAC Systems
Attach the Ultra-Aire return to to a independent return from the 
upper level. Attach the Ultra-Aire supply to the supply of the 
basement HVAC system. This will promote circulation of air through 
the whole structure from the upper level to the lower level through 
the Ultra-Aire . If the Ultra-Aire is not connected to both HVAC 
systems, it will not control the humidity and ventilation of the entire 
structure. Connect a duct from outside to the 6" collar of the Ultra-
Aire if you wish to provide fresh make-up air.
3.4G Installation in a Structure with No Existing 
Forced Air HVAC Systems
When installing the Ultra-Aire in a structure that does not have a 
forced air HVAC system, a single return for the Ultra-Aire should 
be installed in central open area of the structure. 
DO NOT locate 
the return in a bathroom or a kitchen. The supply of the Ultra-
Aire should be located in the remote areas of the structure (such 
as bedrooms, den, etc.). By ducting this way the air inside the 
structure will circulate through the Ultra-Aire to be filtered and 
dehumidified. Connect a duct from outside to the 6" collar of the 
Ultra-Aire if you wish to provide fresh make-up air.
3.5 Quiet Installation
Loosen the compressor mounting bolts from the base of the unit. 
Do not remove the bolts, but loosen them so the compressor 
mounting grommets are not compressed. These bolts are tightened 
at the factory to prevent damage during shipping. Loosening them 
will reduce the amount of compressor vibration. Make sure none 
of the compressor tubes are pressed against the cabinet or front 
panel.
A length of 10 feet or more of acoustical flex ducting on the outlet 
of the Ultra-Aire will reduce air noise from the blower. A length of 
flexible ducting on all Ultra-Aire duct connections is recommended 
to reduce noise and vibration transmitted to rigid ductwork in the 
structure.
4. Controls
The Ultra-Aire can be equipped with various accessories to 
enhance its operation. A remote control panel must be used with 
the Ultra-Aire . There are two remote control panels from which to 
choose. The humidity/fan control panel is used to control humidity 
and the fan. The ventilation timer and humidity control panel is 
used to control ventilation, humidity and the fan.
4.1 Humidity/Fan Control Panel
See Figure 1: The humidity/fan control panel automatically controls 
the humidity of the living space. The humidity/fan control panel 
contains an adjustable humidity control and a fan switch. This 
panel should be mounted in a central area of the structure where 
it can accurately sense the humidity of the air in the living space. 
The panel has small perforations that must remain open to the air 
within the living space for accurate humidity sensing.
The humidity/fan control panel can be used in conjunction with 
the optional fresh air damper. When used with the optional fresh 
air damper, the fan/filter switch will act as a fresh air ventilation 
control. When the switch is ON (in this configuration), the fan will 
run, the fresh air damper will open, and fresh air will be filtered 
and brought into the structure. When the switch is OFF, the fresh air 
damper will close and the fan will operate only when the humidity 
control calls for dehumidification.