T7984 A,B,C ELECTRONIC MODULATING CONTROL THERMOSTATS 
Table 2. Option Settings 
Parameter 
Selection 
T7984 Model 
Reheat Time 
Constant 
Fast (7.5 min.); or Normal 
(15 min.) 
• 
Zero Energy 
Band 
3°F (1.5°C); or 5°F (3°C) 
• 
• 
Setpoint 
Definition 
Heating; Cooling or H/C 
midpoint 
• 
• 
Night 
Setback 
5°F (3°C) heat/cool offset, or 
10°F (5°C) setback / cooling 
shutdown 
• 
• 
Main Sensor  Remote or internal 
• 
• 
• 
Fig. 1. Dimensions in inches (mm) 
INSTALLATION 
Location 
Install the thermostat about 5 ft. (1.5 m) above the floor in an 
area with good air circulation at average temperature 
conditions. 
Do not install thermostat where it may be affected by: 
•   drafts, or dead air spots behind doors and in corners. 
•   hot or cold air from ducts. 
•   radiant heat from sun or appliances. 
•   concealed pipes and chimneys. 
•   unheated (cooled) areas such as an outside wall behind the 
thermostat. 
Mounting
The thermostat can be mounted directly on the wall with or 
without a wallplate or a standard single gang electrical box, or 
double gang with adaptor plate (accessory part 272846). 
CAUTION 
Disconnect power supply to prevent electrical 
shock or equipment damage. 
Wiring
Typical wiring connections are shown in Fig.2 to Fig.7.  Wiring 
connections may be made to the screw terminal block with 2-
18AWG or 1-14AWG, solid or stranded copper wires.  Connect 
the system wires to the thermostat terminals. Push excess wire 
back into hole. Plug hole to prevent drafts. 
Auxiliary screw terminal strip may be used in a junction box 
when the application requires multiple wires to be brought 
down at the thermostat. This can make troubleshooting, 
startup and servicing easier. 
DIP Switch Settings 
T7984 thermostats must be configured for proper operation by  
setting DIP switches.  
T7984B 
Reheat output control action: 7.5 or 15 minutes.  
T7984B,C 
Zero energy band (ZEB): 3°F (2°C) or 5°F (3°C) 
Setpoint adjustment: cooling,centred, heating centred with limit 
override for commissioning.  
Night setback amount: see Table 2 for complete listing of 
option settings.  
T7984A,B,C 
Main sensor, internal or remote.  
Table 3. T7984 DIP Switch Definition 
OUTPUT 2 ON/OFF CPH 
T7984B only  
For more information, see on/off output cycle per hour application note.  
CYCLES/HOUR 
S1 
FAST   8 CPH 
SLOW   4 CPH 
It is possible to fix the number of times per hour the on/off 
output will be energized. 
ZERO ENERGY BAND 
T7984B & C only 
ZEB 
S2 
5°F  (3°C) 
3°F  (1.5°C) 
On models which have 2 outputs, 1 for cooling and 1 for 
heating, it is possible to adjust the zero energy band value 
(dead band between heating and cooling endpoints). 
SETPOINT DIAL DEFINITION 
T7984B & C only 
For more information, see setpoint dial definition & setpoint limitation application note. 
Models with cooling and heating outputs 
»  Setpoint dial centered, 75˚F limitation not active. 
»  Setpoint dial defined as heating, 75˚F limitation active. 
DEFINITION 
S3 
S4 
75°F OVERRIDE 
HEATING DIAL 
COOLING DIAL 
CENTERED HC 
»  Setpoint dial defined as cooling, 75˚F limitation active. 
»  Setpoint dial centered, 75˚F limitation active. 
DAY/NIGHT SETBACK 
T7984B & C only 
HEAT SETBACK 
COOL SETUP 
S5 
10°F  (5°C) 
20°F  (10°C) 
5°F  (3°C) 
5°F  (3°C) 
Night mode setpoints can be adjusted 
to different values depending on the 
application. 
REMOTE SENSOR 
T7984A, B & C  
On model T7984A, switch S7 & S8 are not used.  
MAIN SENSOR 
LOCAL INTERNAL 
REMOTE SENSOR 
For duct return air or remote room sensor control only. 
S6 
Do not use remote sensor in supply or discharge air 
control applications. 
ON = 1 
OFF = 0  1  2  3  4  5  6 
3  
95C-10815–2