The XP-COMPACT (except for 60Hz versions) is equipped with a Flash 
processor fitted out with EEPROM Memory, which means that even when it is 
disconnected from the battery, the parameters that were programmed for the 
application remain after a new connection to the battery. 
It is possible to reinitialize (RESET) the XP-COMPACT by pressing 
simultaneously on the three push buttons 19/20/21 during at least 2 seconds. A 
beep will confirm the RESET. The inverter switches off after this operation. It 
can be turned on again after the beep. The programmed parameters will 
remain. 
5.1 Standard 
setting 
The XP-COMPACT is delivered with the following default settings: 
Auxiliary contact: active in case of defect or manual turn off with the LED 10/11/12/13 
Battery voltage : 
Low voltage 
11.6V / 23.2V / 46.4V 
 
Float Charge 
13.5V / 27.0V / 54.0V 
 
End of Charge Voltage  14.4V / 28.8V / 57.6V 
 
Equalization 
15.6V / 31.2V / 62.4V 
Absorption Time : 
2 Hours 
Equalizing Time : 
20 Minutes 
5.2  Reset value (default settings) 
To come back to the default settings, press simultaneously on the push buttons 
20/21 during at least 2 seconds. A beep will confirm the comeback to the factory 
settings. The inverter switches off after this operation. It can be turned on again after 
the beep. 
5.3  Battery voltages and absorption time 
5.3.1  Set the voltage and timing threshold 
The programming is done in accordance with 
the following steps: 
Push and hold down, the Push Button 21 
(Program) and the Push Button 19 (Change 
status) for minimum 2 seconds 
simultaneously. 
With the Push Button 20 (select) select which 
of the battery level and of the absorption time 
have to be changed. 
These four red LED’s show the function set: 
 
Low voltage 
LED 13 (ON/OFF) 
Float charge 
LED 12 (Batt. Low/high) 
Absorption (End of charge) 
LED 11 (Overload) 
Equalization 
LED 10 (Overtemp.) 
Absorption Time 
LED 10/11/12/13 (altogether)