APPENDIX C - ACCESS CONTROL BY USER CODE 
Page:  91
 
8.3  APPENDIX C - ACCESS CONTROL BY USER CODE 
8.3.1  INTRODUCTION 
Certain critical activities which can be accessed from the 
keypad are initially unrestricted.  Entry  codes can be 
initiated at any time so that these activities are protected 
from unauthorized access. 
8.3.2  DEFINITIONS 
USER NUMBER
: Single digit number between 1 and 8.  This 
number is used to establish different authorized users and 
is printed on reports generated by each user.  User number 
1 must be established before the other numbers can be 
used. 
ENTRY CODE
:  Four digit code between 0001 and 9999.  
This is the access code which is assigned to each user and 
is required to access critical menu items which result in 
changes to the system. 
SPECIAL USER NUMBER
:  The special user number 9 is 
reserved for access to the diagnostic mode of operation. 
DIAGNOSTIC CODES
:  When the user number 9 is used to 
access diagnostics, four digit entry code numbers are used 
to select various diagnostic activity. 
8.3.3  USER CODE INSTALLATION 
1.  Select the 
"SET USER CODE"
 activity via the 
MODE
 key and press 
ENTER
.  Sentry will display 
"USE
 
ARROWS/ENTER"
 
"USER
 
#
 
1".
 
2.  To establish an entry code for user number "1"  
press 
ENTER
 and Sentry will display 
"USE
 
ARROWS/ENTER"
 
"ENTRY
 
CODE
 
=
 
0"
  
3.  Use the arrow to change the first digit as 
required, press 
ENTER
 to move to the second 
digit. 
4.  Set the second, third and fourth digits in the 
same manner. 
5.  When an entry code has been established that 
code must be used to access the controlled 
sections of the menu. 
6.  User numbers 1 through 5 have access to all 
Sentry functions.  Users 6 through 8 are 
restricted to calibration activities only. 
8.3.4  USER CODE REMOVAL 
1.  Change user number 1 entry code to "0000". 
8.3.5  DIAGNOSTIC CODES: 
Select the 
"SET
 
USER
 
CODE"
 activity, input user number 
"9" and press 
ENTER
.  The display will indicate 
"WARNING:
  
DIAGNOSTIC
 
MODE"
 and will then ask for 
the 
ENTRY
 
CODE
.  The following are the codes and their 
Function: 
Code 
Function 
0000 
Clears all warm-up timers. 
0002 
Disables error filtering and reduces all warm-
up times. 
0003 
Not used. 
0004 
Displays critical module electrical 
measurements during normal operation. (H2S: 
Sensor signal & Heater Power in mW, 
Combustible: Sensor signal & Bridge Power 
in mW, O2  & CO: Sensor signal.) 
0006 
Clears printer buffer. 
0007 
Clear module X:  Asks for the module number 
and clears that module's information from the 
system memory. 
0008 
Prints a periodic diagnostic report.  The 
period is selected in the subsequent menu 
selection. (1, 5, 10 , 30 minutes, 1, 8, 12, 24 
hours.) 
0009 
Reset of all diagnostic modes 
0010 
Prints a single diagnostic report 
0012 
Forces all Analog Outputs (Model 4314-01) 
to 4 mA. 
0013 
Forces all Analog Outputs (Model 4314-01) 
to 20 Ma 
0020 
Force Calibrates one sensor module.  Asks for 
the module number after the code is input. 
0021 
Force Calibrates all uncalibrated sensor 
modules. 
0022 
Disables alarm suppression during calibration. 
0023 
Restores alarm suppression during calibration 
0099 
Clears all system RAM including 
configuration, calibration and history data.