Commissioning
Proline Promass 80 PROFIBUS PA
52
6.5.2
Selecting the GSD file in the measuring device
Depending on which GSD file is used in the PROFIBUS master system, the corresponding GSD file 
has to be configured in the device by means of the SELECTION GSD function.
COMMUNICATION 
→ SELECTION GSD
Example
Before configuration takes place, a decision should be made as to which GSD file should be used to 
configure the measuring device in the PROFIBUS master system. Below, the use of the 
manufacturer-specific GSD file (complete device functionality) is shown using PROFIBUS PA as an 
example:
Select the manufacturer-specific GSD file in the measuring device by means of the SELECTION 
GSD function.
COMMUNICATION 
→ SELECTION GSD → Select: MANUFACT. SPEC. (factory setting)
1.
Before configuring the network, load the corresponding GSD file into the configuration 
system/master system.
!
Note! 
When installing the GSD file, always first use the GSD file with the extended format 
(EH3x1528.gsd). However, if the installation or the configuration of the device fails with this 
format, then use the standard GSD (EH3_1528.gsd).
Example for the configuration software Siemens STEP 7 of the Siemens PLC family 
S7-300/400: 
Use the GSD file with the extended format (EH3x1528.gsd). Copy the file to the subdirectory 
"…\siemens\step7\s7data\gsd". The GSD files also include bitmap files. These bitmap files 
are used to display the measuring points in image form. The bitmap files must be saved to the 
directory "…\siemens\step7\s7data\nsbmp".
If you are using configuration software other than that referred to above, ask your PROFIBUS 
master system manufacturer which directory you should use.
2.
The measuring device is a modular PROFIBUS slave, i.e. the desired module configuration 
(input and output data) must be performed in the next step. This can be done directly by means 
of the configuration software. 
6.5.3
imum number of writes 
If a nonvolatile device parameter is modified via the cyclic or acyclic data transmission, this change 
is saved in the EEPROM of the measuring device.
The number of writes to the EEPROM is technically restricted to a maximum of 1 million. Attention 
must be paid to this limit since, if exceeded, it results in data loss and measuring device failure. For 
this reason, avoid constantly writing nonvolatile device parameters via the PROFIBUS!
Promass 80 GSD file
Select: MANUFACT. SPEC. (factory setting)
Profile GSD file
Select: PROFILE-GSD