Whirlpool Water Heater 318686-000 사용자 설명서

다운로드
페이지 24
5
Water supply pressure should be around 50 to 60 psi 
and should not exceed 80 psi. If this occurs, a pressure 
reducing valve should be installed in the cold water inlet 
line. This should be placed on the supply to the entire 
house in order to maintain equal hot and cold water 
pressures.
IMPORTANT
: Heat cannot be applied to the water fi ttings 
on the heater as they may contain nonmetallic parts. 
If solder connections are used, solder the pipe to the 
adapter before attaching the adapter to the hot and cold 
water fi ttings.
IMPORTANT
: Always use a good grade of joint com-
pound and be certain that all fi ttings are drawn up tight.
1.  
Install the water piping and fitting as shown in  
 
 Figure 3. Connect the cold water supply (3/4” NPT)
 
 to the fitting marked “Cold”. Connect the hot water 
 
 supply (3/4” NPT) to the fitting marked “Hot”.
IMPORTANT
: Some models may contain energy saving
heat traps to prevent the circulation of hot water within 
the pipes. Do not remove these inserts.
2.  
The Installation of dielectric unions in both the hot  
 
 and cold water supply lines is recommended for  
 
 ease of removing the water heater for service or  
 
 replacement.
3.  
Some local codes may require, and the manufac- 
 
 turer of this water heater recommends,
 
 installing a mixing valve in the domestic hot water
 
 line as shown in Figure 4. These valves reduce the
 
 point-of-use temperature of the hot water by mixing
 
 cold and hot water and are readily available.   
 
 Contact a licensed plumber or the local plumbing 
 
 authority.
4.  
If installing the water heater in a closed water
 
 system, install a relief valve or expansion tank in
 
 the cold water line as specified under “Closed
 
 System/Thermal Expansion”.
5.  
Install a shut-off valve in the cold water inlet line. It
 
 should be located close to the water heater and be
 
 easily accessible. Know the location of this valve
 
 and how to shut off the water to the heater.
6.  
Install a discharge line from the temperature and  
 
 pressure relief valve in the opening marked “T & P
 
 RELIEF VALVE”. Install as specified under
 
 “Temperature and Pressure Relief Valve”.
7.  
After piping has been properly connected to the
 
 water heater, open the nearest hot water faucet.  
 
 Then open the cold water shut off valve and
 
 allow the tank to completely fill with water. To purge  
 
 the lines of any excess air and sediment, keep the
 
 hot water faucet open for 3 minutes after a constant
 
 flow of water is obtained. Close the faucet and
 
 check all connections for leaks.
In a Closed System use a 
Thermal Expansion Tank.
Pressure Reducing
Valve With Bypass
Main 
Water 
Supply
Cold Water
Supply to
Fixtures
Cold Water
Inlet Valve
Hot Water
Outlet
Union
Temperature and
Pressure Relief Valve
Discharge line 6” maximum
above drain
Drain line
3/4” ID
minimum
Drain
Metal Drain Pan
2-1/2” depth max.
1”
Min.
Massachusetts:
Install vacuum relief
in cold water line per
section 19 MGL 142.
Figure 3
Water Piping Installation
GRID
ENABLED
VACATION
STANDARD
ENERGY
SMART
°F/°C
F
Figure 4
Mixing Valve
Top Water Connections
Unmixed
Hot Water
Mixed Water
To Fixtures
Cold Water
Inlet
Hot
Water
Outlet
Mixing Valve
(Set To 120  F)
0
Follow The Mixing Valve
Manufacturer’s Instructions
Water System Piping
Piping Installation
Piping, fi ttings, and valves should be installed according
to the installation drawing (Figure 3). If the indoor in-
stallation area is subject to freezing temperatures, the 
water piping must be protected by insulation.