Overview of Controller Operation
Technobeam
®
 User Manual
terminator attached to its Data Out connector.      
You can construct terminators by following the instructions below:
Figure 2-4.  Constructing a data cable terminator.
Setting up the Link
Follow the guidelines below when setting up the DMX link:
1.
Do not allow the DMX channel ranges (boundaries) used by two 
different devices on the link to overlap.  Overlapping boundaries can 
disable one or both devices.  See Chapter 3 for more information about 
channel boundaries for Technobeam.  Consult the documentation 
provided with the other devices for their DMX channel ranges.
2.
You can assign two fixtures of the same type (for example, two 
Technobeam fixtures both set to full protocol) to the same DMX 
channel range if you want both fixtures to respond to control 
commands in exactly the same way.
3.
Software uploads (updates):  You must remove or bypass all controllers, 
non-High End Systems fixtures, optoisolators and serial data 
distributors on the link if you want to perform software uploads or 
crossloads as described in the section titled “Upgrading Software” on 
page 2-18
.
Dataflash
®
 AF1000 xenon strobes, Intellabeam
®
 automated luminaires, 
and Emulator
®
 laser simulators will stop software uploads to 
Technobeam fixtures farther down the link.  Make sure you put all of 
the Intellabeam fixtures, Emulator fixtures and AF1000 fixtures after 
all of the Technobeam fixtures.
4.
As long as you observe all of the rules above, you can use whatever 
DMX channels and cabling scheme you want.  You do not, for example, 
have to assign the lowest DMX start channel to the fixture directly 
connected to the controller.  Use whatever channel and cabling scheme 
is simplest and results in the least amount of cabling.
12
0
Ω
 
1.  Obtain a male XLR connector.
2.  Disassemble the connector.
3.  Solder a 120 ohm resistor, minimum
     of 1/4 watt, between pins 2 and 3.
4.  Reassemble the connector.
5.  Install the terminator in the Data Out
     port of the last device in the link.