"UniVert 2" inverter 
 
Page 34 of 42 
8000012364 BAL, en 
- Power cables ............................... Burst test in acc. with 
EN 61000-4-4, 2 kV 
Surge test in acc. with 
EN 61000-4-5, 
2 kV asymmetrical 
- Control cables ............................. Burst test in acc. with 
EN 61000-4-4, 2 kV 
Surge test in acc. with 
EN 61000-4-5, 
2 kV asymmetrical 
Functional extra-low voltage .......... With safe isolation at UO ≤ 60 V DC 
to VDE 0100 Part 410 11.83  
Section 4.3.2 
Overload behaviour ....................... 1.6 x rated current for 1 minute 
1.3 x rated current for 10 minutes 
The mains fuse used must be 
taken into consideration! 
Max. load fusing ............................ gL 40A 
Messages ...................................... - Operation 
 
LED green 
- INV voltage present  LED green 
- Mains volt. present 
LED green 
- Synchronism   
LED green 
- INV supplies the load LED green 
- SBS suppl. the load  LED green  
- Collective fault 
LED red 
Remote signals (X4) ...................... Collective fault signal via potential-
free relay contact X4.1,2,3 
(safe isolation)  
INV operation signal via potential-
free relay contact X4.4,5,6 
(safe isolation) 
Max. contact load: 
150 V DC < 1.6 A 
Min. contact load: 12 V 0.1 A 
Monitoring systems........................ - Load undervoltage 
- Load overvoltage 
- Mains undervoltage 
- Mains overvoltage 
- Heat sink overtemperature 
- Mains / INV synchronism 
- Self-test, watchdog 
- Internal auxiliary voltages 
Design ........................................... 19" mounting rail for installation in 
module rack in acc. with 
DIN 41494