AEG 8000012364 BAL Manual Do Utilizador
"UniVert 2" inverter
Page 34 of 42
8000012364 BAL, en
- Power cables ............................... Burst test in acc. with
EN 61000-4-4, 2 kV
Surge test in acc. with
EN 61000-4-5,
2 kV asymmetrical
Surge test in acc. with
EN 61000-4-5,
2 kV asymmetrical
- Control cables ............................. Burst test in acc. with
EN 61000-4-4, 2 kV
Surge test in acc. with
EN 61000-4-5,
2 kV asymmetrical
Surge test in acc. with
EN 61000-4-5,
2 kV asymmetrical
Functional extra-low voltage .......... With safe isolation at UO ≤ 60 V DC
to VDE 0100 Part 410 11.83
Section 4.3.2
Section 4.3.2
Overload behaviour ....................... 1.6 x rated current for 1 minute
1.3 x rated current for 10 minutes
The mains fuse used must be
taken into consideration!
The mains fuse used must be
taken into consideration!
Max. load fusing ............................ gL 40A
Messages ...................................... - Operation
LED green
- INV voltage present LED green
- Mains volt. present
- Mains volt. present
LED green
- Synchronism
LED green
- INV supplies the load LED green
- SBS suppl. the load LED green
- Collective fault
- SBS suppl. the load LED green
- Collective fault
LED red
Remote signals (X4) ...................... Collective fault signal via potential-
free relay contact X4.1,2,3
(safe isolation)
INV operation signal via potential-
free relay contact X4.4,5,6
(safe isolation)
Max. contact load:
150 V DC < 1.6 A
Min. contact load: 12 V 0.1 A
(safe isolation)
INV operation signal via potential-
free relay contact X4.4,5,6
(safe isolation)
Max. contact load:
150 V DC < 1.6 A
Min. contact load: 12 V 0.1 A
Monitoring systems........................ - Load undervoltage
- Load overvoltage
- Mains undervoltage
- Mains overvoltage
- Heat sink overtemperature
- Mains / INV synchronism
- Self-test, watchdog
- Internal auxiliary voltages
- Mains undervoltage
- Mains overvoltage
- Heat sink overtemperature
- Mains / INV synchronism
- Self-test, watchdog
- Internal auxiliary voltages
Design ........................................... 19" mounting rail for installation in
module rack in acc. with
DIN 41494
DIN 41494