Chapter 5  Trial Run and Tuning Procedure|ASDA-B Series 
Revision January 2009 
 
 
5-9 
5.4  Speed Trial Run without Load 
Before speed trial run, fix and secure the motor as possible to avoid the danger from the reacting 
force when motor speed changes. 
STEP 1: 
Set the value of parameter P1-01 to 4 and it is speed (Sz) control mode. Please ensure to set P1-01 when 
the servo drive is Off (Servo Off). After selecting the operation mode as speed (Sz) control mode, please 
restart the drive as P1-01 is effective only after the servo drive is restarted (after switching power off and on). 
STEP 2: 
In speed control mode, the necessary Digital Inputs are listed as follows: 
Digital Input 
Parameter Setting 
Value 
Sign 
Function Description 
CN1 PIN No. 
DI1 P2-10=101 
SON 
Servo 
On 
DI1-=17 
DI2 
P2-11=109 
TRQLM 
Torque limit enabled 
DI2-=18 
DI3 
P2-12=114 
SPD0 
Speed command selection 0 
DI3-=5 
DI4 
P2-13=115 
SPD1 
Speed command selection 1 
DI4-=3 
DI5 P2-14=102 
ARST 
Alarm 
Reset 
DI5-=15 
DI6 
P2-15=0 
Disabled 
This DI function is disabled 
DI6-=14 
By default, DI4 is the function of reverse inhibit limit, DI5 is the function of forward inhibit limit and DI6 is the 
function of emergency stop (DI6), if the users do not set the setting value of parameters P2-13 to P2-15 to 0 
(Disabled), the faults (ALE13, 14 and 15) will occur (For the information of fault messages, please refer to 
Chapter 10). Therefore, if the users do not need to use these three digit inputs, please set the setting value 
of parameters P2-13 to P2-15 to 0 (Disabled) in advance. Now, we need to use DI4 and D5 (please refer to 
the above table), so it only needs to disable the DI6, i.e. set the setting value of parameter P2-15 to 0. 
All the digital inputs of Delta ASDA-B series are user-defined, and the user can set the DI signals freely. 
Ensure to refer to the definitions of DI signals before defining them (For the description of DI signals, please 
refer to Table 7.A in Chapter 7). 
The speed command is selected by SPD0, SPD1. Please refer to the following table: 
DI signal of CN1  
Speed 
Command No. 
SPD1 
SPD0 
Command Source 
Content 
Range 
S1 0 
0  N/A 
Speed command is 
0(zero) 
N/A 
S2 
P1-09 
-5000 ~ 5000rpm
S3 
P1-10 
-5000 ~ 5000rpm
S4 1 
Internal parameter 
P1-11 
-5000 ~ 5000rpm
0: indicates OFF (Normally Open); 1: indicates ON (Normally Closed)  
If any alarm code displays after the setting is completed, the users can restart the drive or set DI5 to be 
activated to clear the fault. Please refer to section 5.2.