Chapter 6  Control Modes of Operation|ASDA-B Series
 
6-4  
 
Revision January, 2009
 
6.2.3  Pulse Inhibit Input Function (INHP) 
INHP is activated via digital inputs (Please refer to parameter P2-10 ~ P2-15 and DI INHP(07) in Table 
7.A).When the drive is in position mode, if INHP is activated, the external pulse input command is not 
valid and the motor will stop.  
Pulse
command
INHP
ON
OFF
ON
 
 
6.2.4  Electronic Gear Ratio 
Relevant parameters: 
P1 - 15 
  GR4 
Electronic Gear Ratio (2nd Numerator) (N2) 
Communication Addr.: 010FH
Default: 1 
Related Section: 
Applicable Control Mode: P 
Section 6.2.4, P1-44, P1-45 
Unit: pulse 
DI GNUM0(11) in Table 7.A 
Range: 1 ~ 32767 
Settings: 
The electronic gear numerator value can be set via external DI signal (refer to Table 7.A). 
DI  Name 
DI Status 
Selected Electronic Gear 
Not select (Note 1) 
P1-44, P1-45 
0 P1-44, 
P1-45 
GNUM0 
1 P1-44, 
P1-45 
NOTE
 
1)  DI signal can be selected by parameter P2-10 to P2-15 and Table 7.A. If uses only need to 
use one group of electronic gear, it allows users not to select GNUM0. 
 
P1 - 44 
  GR1 
Electronic Gear Ratio (1st Numerator) (N1) 
Communication Addr.: 012CH
Default: 1 
Related Section: 
Applicable Control Mode: P 
Section 6.2.4, P1-15, P1-45 
Unit: pulse 
DI GNUM0(11) in Table 7.A 
Range: 1 ~ 32767 
Settings: 
The electronic gear numerator value can be set via external DI signal (refer to Table 7.A).