Hearth & Home Technologies MBK 사용자 설명서

다운로드
페이지 32
Page 13
Yosemite Wood Stove
7004-187F   September 1, 2008
R
FIGURE 13B
SOLID PACK CHIMNEY WITH METAL SUPPORTS AS A THIMBLE
Add the 19-5/16" (491mm), center-line measurement to 
the depth measurement of your floor protector.  Mark 
this combined measurement at the correct wall location 
for your installation, maintaining minimum clearance 
to combustibles, and mark the wall for a 10 inch x 10 
inch (254mm x 254mm) square hole. The center of the 
square hole should line up with the centerline of the rear 
vent flue pipe, as shown above.
FLOOR PROTECTOR
THIMBLE,
12" (305mm) 
OF BRICK
AIRTIGHT 
CLEANOUT DOOR
SHEATHING
CEILING JOIST
COMBUSTIBLE WALL
1"  (25mm) 
CLEARANCE
FIRECLAY FLUE LINER 
WITH AIR SPACE
EAVE
1" (25mm) 
CLEARANCE 
WITH FIRESTOP
RAFTER
FLASHING
CONCRETE CAP
For the method of installation to a masonry chimney shown in Figures 14A & 14B on page 14, it will be necessary to purchase 
a 12 inch (305mm) long, [8 inch (203mm) inside diameter], section of prefabricated listed solid pack chimney to use as a thimble.  
Purchase a wall spacer, trim collar, and a wall band manufactured to fit the chimney section you purchased.
The safety features of this system are twofold:  1) A 2 inch (51mm) air space between the chimney section and combustible 
wall; and, 2) The 1 inch (25mm) air space around the chimney connector as it passes through the chimney section to 
the chimney.
The location of the opening through the wall to the chimney must leave a minimum 18 inches (457mm) vertical clearance between 
the connector pipe and the ceiling to prevent the ceiling from catching fire.
Measure as shown in Figure 13A.  Cut an opening in the wall large enough to accommodate the outside dimension of the 
chimney section plus the minimum air space specified by its manufacturer.  It may be necessary to cut the wall studs and 
install a header and a sill frame to maintain the wall support.  The hole in the chimney must have at least an 8 inch (203mm) 
diameter fire clay liner or equivalent, secured with refractory mortar.  If it is necessary to cut a hole in the chimney liner, 
use extreme care to keep it from shattering.
WARNING!  ALWAYS FOLLOW CHIMNEY CONNECTOR MANUFACTURER’S INSTRUCTIONS FOR PROPER INSTALLATION.
CHIMNEY CONNECTOR IS TO BE USED ONLY WITHIN THE ROOM, BETWEEN THE STOVE AND CEILING OR WALL, NEVER 
PASSING THROUGH A COMBUSTIBLE CEILING OR WALL.  THE CONNECTOR SHALL NOT PASS THROUGH AN ATTIC OR 
ROOF SPACE, CLOSET OR SIMILAR CONCEALED SPACE, OR A FLOOR, OR CEILING.  MAINTAIN MINIMUM CLEARANCES 
TO COMBUSTIBLES AS REFERENCED ON PAGES 6 & 7. 
FIGURE 13A
Center of 
Hole
Wall
Center 
Line
Opening
Center 
Line
C
L
19-5/16"
(491mm)