Vermont Casting DVT38S2 사용자 설명서

다운로드
페이지 40
11
Chateau™ Decorative Gas Appliance
20009543
Outside Corner
Inside Corner
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors. 
G =
Combustible 
  6" (152 mm)
Noncombustible 
  2" (51 mm)
F =
Combustible 
  6" (152 mm)
 
Noncombustible 
  2" (51 mm)
G
Balcony - 
with no side wall
M = 
Combustible &
Noncombustible
  12" (305 mm)
M
Balcony - 
with perpendicular side wall
M = 24" (610 mm)
P = 20” (508 mm)
M
F
Alcove Applications*
C
D
C
E
V
V
Combustible &
Noncombustible
V
V
V
E
 = Min. 6” (152 mm) for 
non-vinyl sidewalls
Min. 12” (305 mm) for
vinyl sidewalls
O
 = 8’ (2.4 m) Min.
O
P
584-15
 
No. 
  of Caps 
  D
Min.
 
  C
Max.
 
3’ (.9 mm)  2 x D
Actual
 
6’ (1.8 m) 
1 x D
Actual
 
9’ (2.7 m) 
2/3 x D
Actual
 
12’ (3.7 m)  1/2 x D
Actual
D
Min.
 = # of Termination caps x 3
C
Max.
 = (2 / # termination caps) x D
Actual
*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions 
specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All 
mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All 
gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.
Fig. 12  Termination clearances.
General Information Assembling Vent Pipes
SK8 Venting Pipes 
Canadian Installations:
The venting system must be installed in accordance 
with the current CSA-B149 .1 installation code.
USA Installations:
The venting system must conform with local codes and/
or the current National Fuel Gas code  ANSI Z223.1/
NFPA 54.
Only venting components manufactured by CFM Cor-
poration can be used in Direct Vent systems. 
NOTE: The joints of the inner pipe (flue pipe) must be 
taped with 550°F or higher temperature metal adhesive 
tape that meets the requirements of F.A.R. 25.853(a). 
High temperature sealant milpack or stove cement 
of 550°F or higher could be used instead. The joints 
of The outer pipe (fresh air pipe) must be taped with 
315°F or higher temperature metal adhesive tape or the 
use of high temperature milpack or stove cement would 
be applicable. When using the unitized 30°, 45° or 90° 
elbows, apply 1/4” bead of high temperature, 550°F or 
higher, sealant (milpack or stove cement) to the joint of 
the inner pipe (flue pipe) and the straight section as it is 
impossible to be taped. The outer pipe must be taped 
with 315°F high temperature metal adhesive tape for 
proper sealing.
Start by attaching the first vent pipe section to the collar 
on top of the fireplace. In order to attach the first pipe 
section, it may be necessary to remove the top shield. 
Remove four (4) screws securing top shield, install first 
pipe section and replace top shield.
Install the pipe as shown in Figure 14. When you get a 
good lock, you will hear the pipe clearly snap together. 
Once sections are snap-locked in place, it is extremely 
difficult to get them apart. Make sure the pipe is firmly 
snapped and locked together as each pipe section is 
mounted.  
When installing elbows, follow the same procedure.  
The joints of inner and outer elbow must be taped with 
UL approved high temperature metal adhesive tape for