11.2 Begin Start-Up    
11.2.1 Before Operating the Heater
To ensure that all the controls are in safe working 
order, operate the heater for the first time with the 
isolating gas valve turned off and power supply 
turned on.
1. Turn off the isolating gas valve.
2. Turn up the thermostat above room 
temperature. The automatic ignition 
sequence will now begin as described 
on Page 28, Figure 13.
There will be no ignition of the burner and lockout 
will occur, which proves the controls are operating 
correctly.
Figure 13: Automatic Burner Control Sequence
Burner Sequence for Ignition Control
Flame Signal
Start Gas Valve
Ignition Spark
Thermostat 24 V
SHUT DOWN
RUN
START
 ts = 10 Seconds
Signals Output By Control
Required Incoming Signals
Flue Blower
Pressure
Switch
P
C
NO
NC
30 Seconds Purge*
*Purge time begins at pressure switch change over.
Axial Fan
30 Seconds Delay
90 Seconds Delay
30 Seconds Post Purge
If at any stage the flame fails, the control will retry 
for ignition. The control has four trials for ignition 
before a one hour lockout.