11.2.2 Start-Up the Gas Valve (All Gases)
11.2.2.1 Check Burner Gas Pressure
1. Remove the plug in the outlet (burner) pressure 
test point and connect a pressure tap and a 
manometer.
2. With the burner firing, measure the pressure on 
the manometer. To adjust the burner pressure, 
remove the regulator cover from the valve and 
turn the regulator adjustment screw to set the 
required burner pressure as stated in the 
Technical Data Table for the correct gas and 
model 
on Page 49, Section 16.3.
NOTE: If the correct burner pressure cannot be 
reached, then check the inlet pressure to the valve 
with the burner firing. See Technical Data Table 
on 
Page 49, Section 16.3 for inlet pressure 
requirement.
Do not continue to adjust the regulator if the 
pressure is not changing.
If the inlet pressure is too low to allow correct burner 
pressure setting, then the gas inlet pressure must be 
corrected before completing the start-up. 
Check Gas Rate
1. After burner pressure adjustment, allow the 
heater to operate for at least 15 minutes and 
then re-check settings. Adjust pressure setting 
if necessary.
2. Check gas flow rate at gas meter.
3. Turn off heater and electrical supply.
4. Remove the manometer and refit all covers to 
the valve and tighten the screw of the outlet 
pressure tap.
11.2.3 Pressure Switch
The pressure switch is factory pre-set for each 
model and is not adjustable.
11.2.4 Turning Off the Heater
Set the thermostat to the "OFF" position or lowest 
setting and the main burner will stop.
The fan will continue to run until it is stopped 
automatically by the fan thermostat. 
Do not use a disconnect switch for control of 
heater. Disconnect switch will turn off the fan. 
Heat exchanger could be damaged. Warranty will 
not cover damage to the heat exchanger if 
operated improperly. Only use the disconnect 
switch for turning off heater for service or during 
off-season.