installation
2.   External termination of condensate drainage pipe via internal 
discharge branch (e.g. sink waste) and condensate trap.
3.   External termination of condensate drainage pipe via internal 
discharge branch (e.g. sink waste - proprietary fi tting).
4.   External termination of condensate drainage pipe via condensate 
trap
Condensate Discharge
The condensate discharge hose from the boiler must have a 
continuous fall of 2.5
o
 and must be inserted by at least 50mm into 
a suitable acid resistant pipe - e.g. plastic waste or overfl ow  pipe.  
The condensate discharge pipe must have a minimum diameter of 
22mm, must have a continuous fall and preferably be installed and 
terminated to prevent freezing.
The discharge pipe must be terminated in a suitable position:
i)    Connecting into an internal soil stack (at least 450mm above the 
invert of the stack). A trap giving a water seal of at least 75mm 
must be incorporated into the pipe run, there also must be an air 
beak upstream of the trap.
ii)  Connecting into the waste system of the building such as a 
washing maching or sink trap.  The connection must be upstream 
of the washing machine/sink.  If the connection is downstream of 
the waste trap then an additional trap giving a minimum water 
seal of 75mm and an air break must be incorporated in the pipe 
run, as above.
iii)  Terminating into a gully, below the grid level but above the water 
level
iv)  Into a soakaway
Note: If any condensate pipework is to be installed externally then 
it should be kept to a minimum and be insulated with a waterproof 
insulation and have a continuous fall.  The total length of external 
pipe used should not exceed 3 metres.
Some examples of the type of condensate terminations can be found 
below.
1.   Internal termination of condensate drainage pipe to internal 
stack.
trap
trap