Connecting the Flue
 Flue  System
The provision for satisfactory fl ue termination must be made as 
described in BS 5440-1.
The appliance must be installed so that the fl ue terminal is exposed 
to outdoor air.
The terminal must not discharge into another room or space such as 
an outhouse or lean-to.
It is important that the position of the terminal allows a free passage 
of air across it at all times.
The terminal should be located with due regard for the damage or 
discolouration that might occur on buildings in the vicinity, it must 
also be located in a place not likely to cause nuisance.
In cold or humid weather water vapour may condense on leaving the 
fl ue terminal.
The eff ect of such “steaming” must be considered.
If the terminal is less than 2 metres above a balcony, above ground or 
above a fl at roof to which people have access, then a suitable stainless 
steel terminal guard must be fi tted. 
The minimum acceptable spacing from the terminal to obstructions 
and ventilation openings are specifi ed in Fig. 1.
Where 2 or more vertical fanned draught chimney confi gurations 
teminate in close proximity at the same height they shall be separated 
by at least 300mm. Where any 1 vertical outlet is more than 300mm 
above the other, then they shall be separated by at least 1500mm.
Fig. 1
- A  Directly below an opening, window, etc 
300 mm
- B  Horizontally to an opening, window, etc 
300 mm
- C  Below gutters, soils pipes or drain pipes 
75 mm
- D  Below eaves 
200 mm
- E  From vertical drain pipe or soil pipe 
75 mm
- F  From internal or external corner 
300 mm
- G  Above ground, roof or balcony level 
300 mm
- H  From a surface facing the terminal 
600 mm
- I   From a terminal facing a terminal 
1200 mm
- J   Vertically from a terminal on the same wall 
1500 mm
- K  Horizontally from an terminal on the same wall 
300 mm
- L  Fixed by vertical fl ue terminal
118 mm
See table 
118 mm
4
See table on page 22
180
Fig. 2
Warning
The exhaust gas ducts must not be in contact with or close to 
infl ammable material and must not pass through building structures 
or walls made of infl ammable material.
When replacing an old appliance, the fl ue system must be changed. 
Important
Ensure that the fl ue is not blocked.
Ensure that the fl ue is supported and assembled in accordance with 
these instructions.