installation
  (b)
  (d)
  (a)
  (e)
  (c)
Instructions for opening the casing and performing an 
internal inspection
Before performing any work on the boiler, fi rst disconnect it from the 
electrical power supply using the external bipolar switch; removing 
the fuse and shutting off  the gas cock.
To access the inside of the boiler, the following is necessary:
1.  Remove the casing by unhooking it from the control panel (a)
2.  Loosen the two screws on the front casing (b), pull it forwards and 
unhook it from the upper pins (c)
3.  Lower the control panel (d)
4.  Unhook the two clips on the combustion chamber panel and lift 
off  (e).
To calculate the size of the heating installation, refer to the "Available 
pressure" graph below. 
Graph representing the available circulation pump 
pressure 
ΔT20
o
C
 
 Before the equipment is used, for the fi rst time the trap must 
be fi lled with water. To do this, add approximately 1/4 litre of 
water via the fl ue outlet before fi tting the fl ue system, or uns-
crew the cap on the trap positioned underneath the boiler, fi ll 
it with water and refi t it.
  Warning! 
 Insuffi
  cient water in the trap can temporarily cause the fl ue 
gas to be expelled into the surrounding ambient air.
A
B
C
D
E
I
G
H
F
0
50
100
150
200
250
300
350
400
450
500
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
mbar
l/h
24 kW
30-35 kW
30-38 kW