Ariston E-COMBI 24 30 38 Manual Do Utilizador

Página de 56
21
installation
Fitting the Twin Pipe (Ø80 / 80)
Fig. 8
Fig. 8a
Before proceeding to fi t the fl ue, ensure that the maximum fl ue 
length has not been exceeded (see the tables) and that all elbows and 
bends have been taken into consideration. For each additional 90° 
elbow 1 metre must be subtracted from the maximum fl ue length, 
and for each 45° 0.5 metres must be subtracted from the maximum 
fl ue length (the height of the vertical adaptor and a 45° bend can be 
seen in Fig. 8).
 Note: See table for maximum and minimum fl ue runs.
Where it is not possible to terminate the fl ue within the distance 
permitted for coaxial fl ues, the twin fl ue pipe can be used by fi tting a 
special adaptor to the fl ue connector and using the aperture for the 
air intake located on top of the combustion chamber.
Always ensure that the fl ue is adequately supported, using one fl ue 
bracket per extension and avoiding low points. (ARISTON supply 
suitable clamps as Part No. 3318015).
To utilise the air intake it is necessary to:
1) Take the air intake cover off  the top of the appliance
2) Assemble the air inlet adaptor - see fi g. 8a
The twin fl ue pipes can be fi tted with or without additional elbows 
and need no clamps, simply ensure that the red o-ring is inserted in 
the female end of the fl ue pipe and push the extension piece fully 
into the previous section of fl ue pipe or elbow. Check that the o-ring 
is not dislodged when assembling the fl ue (greasing the seal will aid 
assembly).
When running the twin fl ue pipe vertically it can be converted back to 
coaxial fl ue to enable vertical termination with a coaxial kit by use the 
pipe bridge (Twin - Coaxial Adaptor - Part No. 3318089).
It is not possible to terminate concentrically horizontally.  Termination 
is only possible with separate air and exhaust terminals. 
When siting the twin fl ue pipe, the air intake and exhaust terminals 
must terminate on the same wall, the centres of the terminals must 
be a minimum of 280 mm apart and the air intake must not be sited 
above the exhaust terminal (refer to Fig. 10).  The air intake pipe can 
be run horizontally, however, the terminal and the fi nal 1 metre of fl ue 
must be installed either horizontally or with a slight fall away from the 
boiler to avoid rain ingress.
It is also strongly recommended that the air intake pipe run be 
constructed of insulated pipe to prevent condense forming on the 
outside of the tube.
Mark the position of the fl ue hole in the ceiling and/or roof (see Fig. 7 
for distance from wall to the centre of the fl ue).
Cut a 130mm diameter hole through the ceiling and/or roof and fi t 
the fl ashing plate to the roof.
DO NOT cut the vertical fl ue kit.
To connect the vertical fl ue kit directly to the boiler, place the vertical 
starter kit (Part No. 3318079) (see Fig. 7) onto the exhaust manifold 
and secure with the clamp, fi t the vertical adaptor onto the vertical 
starter kit (Note: there is no need to use a clamp to secure this as it 
is a push fi t connection), the vertical fl ue kit must then be inserted 
through the roof fl ashing, this will ensure that the correct clearance 
above the roof is provided as the terminal is a fi xed height.
Should extensions be required, they are available in 1 metre (Part 
No. 3318077) and 500mm (Part No. 3318078) lengths. They must be 
connected directly to the vertical starter kit before connecting the 
adaptor to allow the vertical fl ue kit to be fi tted. In the event that 
extension pieces need to be shortened, they must only be cut at the 
male end and it must be ensured that the inner and outer fl ue remain 
fl ush.
 When using the vertical fl ue system, action must be taken to ensure 
that the fl ue is supported adequately to prevent the weight being 
transferred to the appliance. Use 1 fl ue bracket per extension.
When the fl ue passes through a ceiling or wooden fl oor, there must 
be an air gap of 25mm between any part of the fl ue system and any 
combustible material.  The use of a ceiling plate will facilitate this.  
Also when the fl ue passes from one room to another a fi re stop must 
be fi tted to prevent the passage of smoke or fi re, irrespective of the 
structural material through which the fl ue passes.