Ariston E-COMBI 24 30 38 Manual Do Utilizador

Página de 56
25
installation
Room Thermostat / Remote Clock Connection
The boiler connections for external controls are 12V DC and so only 
controls of 12V  DC that have voltage free contacts should be used.
The boiler connections for external controls are 12V DC and so only 
controls of 12V  DC that have voltage free contacts should be used.
To connect a room thermostat, it is necessary to:
1.   Open the control panel
2. Loosen the cable clamp using a screwdriver and insert the wires 
leading from the room thermostat
3.  Connect the wires to the terminals as indicated in the fi gure below, 
removing the link
4.  If a remote time clock is to be fi tted, (using a volt free switching time 
clock) connect the switching wires from the time clock following 
points 1 - 3 above (Disconnect internal time clock)
5. If using an external time clock and room thermostat, these must be 
connected in series as shown in diagram C, (Disconnect internal 
time clock)
6. Ensure that they are well connected and not subject to stress when 
the control panel is closed
N
OTE
: W
HEN
 
CONNECTING
 
THE
 
BOILER
 
TO
 
EXTERNAL
 
CONTROLS
DO
 
NOT
 
RUN
 240V 
CABLES
 
FOR
 
SWITCHING
 
CIRCUITS
  (
WHICH
 
ARE
 
LOW
 
VOLTAGE
TOGETHER
 
USE
 
SEPERATE
 
CABLES
 
TO
 
PREVENT
 
INDUCED
 
VOLTAGE
 
ON
 
THE
 
LOW
 
VOLTAGE
 
CIRCUITS
.
Note: y plan system switch 240v and are therefore not suitable 
system control systems unless a suitable relay is used to switch the 
low voltage control circuit.
Do not connect 240v to the TA1 switching circuit. Connectiong 240v 
to the TA1 switching circuit will damage th P.C.B. and invalidate 
appliance warranty.
   Connector TA on Terminal block
(low voltage switching)
   Connector TA on Terminal block
(low voltage switching)
   Connector TA on Terminal block
(low voltage switching)