4. Position the wallplate over the holes, pulling wires
through the wiring opening. See Fig. 6.
5. Insert the mounting screws into the holes and tighten.
Fig. 6. Mounting wallplate.
WIRING (FIG. 9 - 21)
All wiring must comply with local electrical codes and
ordinances.
1. Select set of terminal identifications (Table 1) that
corresponds with system type (conventional or heat
pump in Fig. 7).
2. Loosen the screws for the appropriate system type
selected; see Table 1. See Table 2 for terminal
designation descriptions. Insert wires in the terminal
block under the loosened screw. See Fig. 8.
3. Securely tighten each screw.
4. Push excess wire back into the hole.
5. Plug the hole with nonflammable insulation to prevent
drafts from affecting the thermostat.
6. See Fig. 9 through 21 for typical wiring hookups.
Fig. 7. Selecting terminal identifications for
system type.
Fig. 8. Inserting wires in terminal block.
IMPORTANT
Use 18 gauge thermostat wire.
WALL
MOUNTING
HOLES
HOLES
M19916
MOUNTING
SCREWS (2)
SCREWS (2)
WALL ANCHORS (2)
WIRES THROUGH WALL
AND WIRE SLOT
AND WIRE SLOT
CONVENTIONAL
SCREW TERMINALS
HEAT PUMP
M19951
Y2
L
E
AUX
S1
S2
Y2
W2
S1
S2
RC
R
O/B
Y
G
C
RC
R
W
Y
G
C
Table 1. Selecting Terminal Identifications for
System Type.
System Type
Wallplate
Terminal
Identifications
Wiring
Diagram
Reference
Standard Heat/Cool
Conventional
9, 10
Heat Only
Conventional
11
Heat Only with Fan
Conventional
12
Heat Only (Series 20)
Power to open and
power to close zone
valves
Conventional
13
Normally Open Zone
Valves—Heat Only
Conventional
14
Cool Only
Conventional
15
Standard Multistage up
to 2 Heat/2 Cool
Conventional
16, 17
Heat Pump with No
Auxiliary Heat
Heat Pump
18, 19
Heat Pump with
Auxiliary Heat
Heat Pump
20, 21