Chapter 2: Installing and Configuring the EMX Device 
 
36
 
 
 
Connecting Detectors/Switches to DPX-CC2-TR 
A DPX-CC2-TR unit provides two channels for connecting two discrete 
(on/off) detectors/switches. There are four spring-loaded termination 
points on the body of DPX-CC2-TR: the two to the right are associated 
with one channel (as indicated by the LED number), and the two to the 
left are associated with the other. You must plug discrete 
detectors/switches into these termination points. 
 
To connect third-party or Raritan's discrete detectors/switches: 
1.  Strip the insulation around 12mm from the end of each wire of 
discrete detectors/switches. 
2.  Press and hold down the tiny rectangular buttons above the 
termination points on the body of DPX-CC2-TR. 
Note: Each button controls the spring of each corresponding 
termination point. 
 
3.  Fully insert each wire of both detectors/switches into each 
termination point. 
  Plug both wires of a detector/switch into the two termination 
points to the left. 
  Plug both wires of the other detector/switch into the two 
termination points to the right. 
 
4.  Release the tiny rectangular buttons after inserting the wires 
properly. 
5.  Verify that these wires are firmly fastened. 
6.  If any detector/switch plugged into the contact closure sensor is 
Raritan's floor water sensor, verify that the total cable length from the 
port of the Raritan PX to the water detector at the end of the water 
sensor does not exceed 30 meters/100 feet.