Chapter 2: Installing and Configuring the EMX Device 
 
 
39
 
 
  Plug both wires of the other detector/switch into the two 
termination points to the right. 
 
4.  Release the tiny rectangular buttons after inserting the wires 
properly. 
5.  Verify that these wires are firmly fastened. 
6.  By default the open status of the detector/switch is considered 
normal. To set the "normal" setting to "closed" , press down the 
corresponding button adjacent to the termination points. 
 
Contact Closure Sensor LEDs 
Two LEDs are located near the contact closure termination points on the 
EMX device or Raritan contact closure sensor module (DPX-CC2-TR). 
Each LED shows the state of the corresponding channel. 
The LED is lit when the associated detector/switch is in the "abnormal" 
state, which is the opposite of the Normal state. 
The meaning of a lit LED varies depending on the Normal state settings. 
 
When the Normal state is set to Normally Closed (N.C): 
LED 
Sensor state 
Not lit 
Closed 
Lit 
Open 
 
 
When the Normal state is set to Normally Open (N.O): 
LED 
Sensor state 
Not lit 
Open 
Lit 
Closed