Chapter 2: Installing and Configuring the EMX Device 
 
40
 
 
 
Connecting Differential Air Pressure Sensors 
You can have a Raritan differential air pressure sensor connected to the 
EMX device if the differential air pressure data is desired. 
With this sensor, the temperature around the sensor can be also 
detected through a temperature sensor implemented inside it. 
Multiple differential air pressure sensors can be cascaded. 
 
To connect differential air pressure sensors: 
1.  Plug one end of a Raritan-provided phone cable to the SENSOR port 
of the EMX device. 
2.  Plug the other end of this phone cable to the IN port of the differential 
air pressure sensor. 
3.  To connect additional Raritan differential air pressure sensors, do the 
following: 
a.  Plug one end of a Raritan-provided phone cable to the OUT port 
of the previous differential air pressure sensor. 
b.  Plug the other end of this phone cable to the IN port of the 
newly-added differential air pressure sensor. 
c.  Repeat Steps a to b to cascade more differential air pressure 
sensors. Note that each SENSOR port supports a maximum of 
16 environmental sensors. 
 
 
The EMX device 
 
The Raritan differential air pressure sensor