PVI Industries PV500-43 Manual Do Utilizador
PV500-43
PVI Industries, LLC P.O. Box 7124 Ft. Worth, TX 76111 1‐800‐433‐5654
Page | 3 7/10
Dip switches A0 to A7 configure the serial address. The table below lists the settings up to 10. The full
257 address settings can be found in the ProtoCessor Getting Started (T17007) manual at
www.protocessor.com
257 address settings can be found in the ProtoCessor Getting Started (T17007) manual at
www.protocessor.com
Dip switches B0 to B3 configure baud rate.
The table below lists the settings.
Dip switches S0 to S3 select the register profile to be used. When
switch S0 is On the register profile will only monitor one control
with an node address of 1. All registers are analog/16bit.
switch S0 is On the register profile will only monitor one control
with an node address of 1. All registers are analog/16bit.
When switch S0 is Off and S1 is On the register profile will monitor
up to 8 controls. The register addresses are detailed below. The
respective node addresses are 1 to 8.
up to 8 controls. The register addresses are detailed below. The
respective node addresses are 1 to 8.
A7
A6
A5
A4
A3
A2
A1
A0
Address
Off
Off
Off
Off
Off
Off
Off
Off
0
Off
Off
Off
Off
Off
Off
Off
On
1
Off
Off
Off
Off
Off
Off
On
Off
2
Off
Off
Off
Off
Off
Off
On
On
3
Off
Off
Off
Off
Off
On
Off
Off
4
Off
Off
Off
Off
Off
On
Off
On
5
Off
Off
Off
Off
Off
On
On
Off
6
Off
Off
Off
Off
Off
On
On
On
7
Off
Off
Off
Off
On
Off
Off
Off
8
Off
Off
Off
Off
On
Off
Off
On
9
Off
Off
Off
Off
On
Off
On
Off
10
Baud
B3
B2
B1
B0
Auto
3
Off
Off
Off
Off
110
Off
Off
Off
On
300
Off
Off
On
Off
600
Off
Off
On
On
1200
Off
On
Off
Off
2400
Off
On
Off
On
4800
Off
On
On
Off
9600
Off
On
On
On
19200
On
Off
Off
Off
20833
On
Off
Off
On
28800
On
Off
On
Off
38400
On
Off
On
On
57600
On
On
Off
Off
76800
On
On
Off
On
115200
On
On
On
Off
Control
Discription
Modbus
Address
BACnet
Address
Temptrac
Set Point Read/Write
40769
1
Temptrac
Temp. Probe 1 Read Only
40257
90
Temptrac
Temp. Probe 2 Read Only
40259
91
Temptrac
Temp. Probe 3 Read Only
40261
92
Temptrac
On/Off Enable Read/Write
401281
95
XR10CX
Temp. Probe 1 Read Only
40257
90
XR10CX
Set Point Read/Write
40854
101
CONFIGURATION SETTINGS TEMPTRAC & XR10CX
Off‐‐‐On