Honeywell T7200E Manual Do Utilizador

Página de 36
T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
63-4355—4
20
T7200/T7300 and Conventional Thermostats
P+I Control
The T7200/T7300 microprocessor based control requires that 
the user understands temperature control and thermostat 
performance. A conventional electromechanical or electronic 
thermostat does not control temperature precisely at setpoint. 
Typically, there is an offset (droop) in the control point as the 
system load changes. This is a phenomenon that most people 
in the industry know and accept. Many factors contribute to 
offset including switch differential, thermal lag, overshoot, 
cycle rates and system load.
The thermostat microprocessor simultaneously gathers, 
compares and computes data. Using this data, it controls a 
wide variety of functions. The special proprietary algorithm 
(program) in the thermostat eliminates the factors causing 
offset. This makes temperature control more accurate than 
the conventional electromechanical or electronic thermostats. 
The temperature control algorithm is called proportional plus 
integral (P+I) control.
The thermostat sensor, located on the thermostat or remote, 
senses the current space temperature. The proportional error 
is calculated by comparing the sensed temperature to the 
programmed setpoint. The deviation from the setpoint is the 
proportional error.
The thermostat also determines integral error, which is a 
deviation based on the length of error time. The sum of the 
two errors is the (P+I) error. The cycle rate used to reach and 
maintain the setpoint temperature is computed using the P+I. 
The addition of the integral error is what differentiates the 
thermostat from many other electronic and electromechanical 
thermostats. See Fig. 18.
Fig. 18. Proportional temperature control 
versus P+I temperature control.
Equipment Protection
As part of the operational sequence, the T7200/T7300 
microprocessor also incorporates minimum on and off times 
for all heating and cooling stages. Minimum on time is set in 
the installer setup number 32. Using the minimum on and off 
times assures that rapid cycling of equipment does not occur, 
which extends equipment life. Minimum on and off times are 
set in the Installer Setup.
T7200/T7300 Thermostat Operation
Startup
When power to the thermostat is turned on, a startup and 
initialization program begins. The startup occurs only on initial 
powerup. After total loss of power for an extended period, the 
current time and day may need to be set, but the user 
program is held. The initial default values are heating 68°F 
(20°C) and cooling 78°F (26°C) for the Occupied periods. 
Unoccupied default values are heating 55°F (13°C) and 
cooling 90°F (32°C).
NOTE:
The thermostat controls to the Unoccupied default 
setpoints of 55°F (13°C) for heat and 90°F (32°C) for 
cool when no program is set.
Occupied Operation
When the thermostat is operating in the Occupied period, 
the temperature is controlled to the occupied heat or cool 
setpoint. The normally open (A1) auxiliary relay contacts are 
closed and the normally closed (A3) auxiliary relay contacts 
are opened during the Occupied periods (if the subbase being 
used has this option). The fan operates as follows: fan 
selection can be set to On (always energized) or Auto (cycles 
with Y1 or W1).
Unoccupied Operation
When the thermostat is operating in the Unoccupied period, 
the temperature is controlled to the Unoccupied heat or cool 
setpoint. The normally open (A1) relay contact is open and the 
normally closed (A3) relay contact is closed. The fan operates 
as follows: fan is always intermittent (cycles with Y1 or W1).
Intelligent Recovery® Feature
Intelligent Recovery is a Honeywell trademarked feature 
for the way the thermostat controls heating and cooling 
equipment during recovery from the Unoccupied to Occupied 
setting. During recovery, the control point changes gradually 
rather than shifting immediately from the energy saving 
setting to the comfort setting.
When Intelligent Recovery is used in heating, the control point 
raises gradually, maximizing the use of the more economical 
first stage heat to bring the sensed temperature to the desired 
comfort setpoint. This minimizes using the typically more 
expensive second-stage heat.
Advantages of Intelligent Recovery are:
Comfort setting is achieved at the programmed time and 
maintained regardless of weather conditions; occupants 
are comfortable.
Drafts from low-temperature discharge air are minimized 
during Occupied periods.
The more economical first stage of heat is the primary heat 
source during recovery, minimizing use of the expensive 
second-stage heat.
Comfort and energy savings can be achieved in both 
heating and cooling.
Heat cycling reduced, extending equipment life.
RECOVERY FROM UNOCCUPIED
The heat pump heat recovery ramp is 3°F (1.6°C) per hour. 
This differs from the 5°F (2.8°C) per hour for conventional 
systems. The 3°F helps the system use the economical heat 
pump more and the expensive auxiliary heat less. The cooling 
ramp is 5°F, the same as for conventional systems.
HEATING
COOLING
PERCENT LOAD
TEMPERATURE
THERMOSTAT
HEAT SETPOINT
P+I CONTROL
POINT
PROPORTIONAL COOL 
CONTROL POINT
THERMOSTAT 
COOL SETPOINT
P+I CONTROL POINT
PROPORTIONAL HEAT 
CONTROL POINT
M4414
100
50
0
50
100