Patterson-Kelley TBIG-03 Manual Do Utilizador
Gemini™ Twin-Fuel Gas-Fired Boiler
lines for gas devices. See Section 4 below.
· Hazard from incorrect fuels! Possible fire, explo-
sion, overheating, and damage. Do not use any
fuels except vaporized natural gas and propane.
Under no circumstances is liquid fuel of any kind
to be introduced in the boiler.
fuels except vaporized natural gas and propane.
Under no circumstances is liquid fuel of any kind
to be introduced in the boiler.
· Hazard from incorrect fuel connections! Possible
fire, explosion, overheating, and damage. Do not
attempt to connect the propane supply to the natu-
ral gas connection, or vice versa.
attempt to connect the propane supply to the natu-
ral gas connection, or vice versa.
· Fire and explosion hazards! Close both the natural
gas and propane shutoffs before servicing boiler.
· Burn hazard! Possible hot surfaces. Do not touch
gas vent during firing operation. Use only factory
recommended B-vent components.
recommended B-vent components.
· Fire and explosion hazards! Use caution when
servicing burner. Propane is heavier than air and
may linger in the combustion chamber, vent lines,
or elsewhere.
may linger in the combustion chamber, vent lines,
or elsewhere.
· Gas leak hazard! Make sure all connections to
main burner are tight when reassembling the
burner. These connections cannot be tested after
burner is assembled.
burner. These connections cannot be tested after
burner is assembled.
· Gas leak hazard! Test motorized gas valves annu-
ally for leakage as described in Section 4.4.6.
· Gas leak hazard! All threaded gas connections
must be made using a pipe compound that is resis-
tant to propane. Do not use Teflon
tant to propane. Do not use Teflon
ä tape on
threaded gas piping.
· Gas leak hazard! Check entire gas train for leaks
after installation. If there is a smell of gas, shut
down the boiler and obtain immediate assistance
from trained service personnel and/or your local
fire department.
down the boiler and obtain immediate assistance
from trained service personnel and/or your local
fire department.
· Overfire hazard! Possible fire and explosion from
excess gas pressure. Make sure that gas inlet pres-
sure does not exceed 14 inches W.C. to the
regulator on either the natural gas or propane sup-
ply line.
sure does not exceed 14 inches W.C. to the
regulator on either the natural gas or propane sup-
ply line.
· Overfire hazard! Possible fire and explosion.
Possible malfunction of regulators and/or motorized
gas valves. Maintain all gas train components in
gas valves. Maintain all gas train components in
good condition. Do not alter wiring connections.
Annual inspection by factory-trained personnel for
proper set-up and operation is recommended.
Annual inspection by factory-trained personnel for
proper set-up and operation is recommended.
· Overfire and underfire hazards! Possible fire, ex-
plosion, overheating, and component failure. Do
not attempt to adjust firing rate of the boiler. The
firing rate must be adjusted only by factory
trained personnel.
not attempt to adjust firing rate of the boiler. The
firing rate must be adjusted only by factory
trained personnel.
3
.5.3 Crush Hazards
General Warning
· Lifting hazards! Use properly rated lifting equip-
ment to lift and position the boiler. The load is
unbalanced. Test balance before lifting 3 ft.
above the floor. Do not allow personnel beneath
the lifted load. Refer to approximate weights in
the table below:
unbalanced. Test balance before lifting 3 ft.
above the floor. Do not allow personnel beneath
the lifted load. Refer to approximate weights in
the table below:
Boiler Size
Weight in Pounds
700,000 Btu
650
1,000,000 Btu
650
1,200,000 Btu
765
1,500,000 Btu
1,100
1,700,000 Btu
1,100
2,000,000 Btu
1,100
3
.5.4 Chemical Hazards
· Environmental hazard! The motorized gas valves
may contain hydraulic oil. Use safe procedures
for the disposal of all lubricants.
for the disposal of all lubricants.
- 4 -