Weil-McLain PLUS LINE PLUS-E017-A/1206 Manual Do Utilizador

Página de 68
Part Number PLUS-E017-A/1206
2
Manual
   • Installation   • Start-Up   • Usage   • Maintenance   • Parts
Install system water piping 
(space heating)
Figure 11 
Expansion tank piping
B1
Gas
System water piping 
methods
 All piping methods shown in this manual
use primary/secondary connection to the
boiler loop. These designs ensure proper
flow  through  the
 Gas  boiler,  for
the most efficient and reliable operation
of the boiler and the heating system. For
other piping methods, consult your local
Weil-McLain  representative  or  refer  to
separate
Gas boiler piping guides.
Wall-mounted boilers — Piping can exit
bottom of boiler enclosure. See separate
wall-mounting instructions for details.
Expansion tank and make-up 
water
1.  Ensure expansion tank size will handle boiler and
system  water  volume  and  temperature.  Allow  
gallons for the boiler and its piping.
 Undersized expansion tanks cause system
water  to  be  lost  from  relief  valve  and
make-up water to be added through fill
valve.  Eventual  boiler  failure  can  result
due  to  excessive  make-up  water  addi-
tion.
2.  Tank must be located as shown in this supplement,
or following recognized design methods. See tank
manufacturer’s instructions for details.
.  Connect  the  expansion  tank  to  the  air  separator
only if the separator is on the suction side of the
system circulator. Always install the system fill con-
nection  at  the  same  point  as  the  expansion  tank
connection to the system.
.  The  piping  drawings  in  this  manual  show  only
diaphragm expansion tanks. Use only bladder-type
or diaphragm-type tanks with PLUS indirect water
heater applications.
.  Refer to the
Boiler Manual for other system
piping examples.
Diaphragm (or bladder) expansion tank
1.  Always install an automatic air vent on top of the air
separator to remove residual air from the system.
2.  See Figure 11 for correct location of the expansion
tank.
DO NOT USE a closed-type expansion tank 
The  boiler-side  piping  must  be
equipped  with  a  diaphragm-  or
bladder-type expansion tank, NOT
a closed-type expansion tank. This
is  necessary  to  allow  venting  air
from the top of the indirect water
heater boiler-side.
Boiler circulator
The boiler circulator is shipped loose. It must be located
in either the return or supply piping, as shown in the
appropriate piping diagram in this supplement or the
Boiler Manual.
 DO NOT use the boiler circulator in any
location other than those shown in this
manual or the boiler manual. The boiler
circulator is selected to ensure adequate
flow through the
boiler. Failure to
comply  could  result  in  unreliable  per-
formance and nuisance shutdowns from
insufficient flow.
Sizing space heat system 
piping
1.  See Figures 12 and 1, pages 2 and 2, or the
Gas Boiler Manual for recommended piping. In all
diagrams, the space heating system is isolated from
the boiler loop by the primary/secondary connec-
tion.
2.  Size the piping and components in the space heating