Wiring a system circulator
1.  For combined systems, to activate a system circu-
lator when the Boiler circulator operates, wire as
shown at bottom of Figure 1, page 0.
2.  You must install a relay as shown. DO NOT wire in
parallel with the Boiler circulator. See
CAUTION
in
Figure 1.
Routing line voltage wiring
1.  Route line voltage connections to the jacket open-
ings shown in Figure 18.
Low voltage connections 
(Fig. 18)
1.  Connect low voltage wiring to low voltage termi-
nal strip (Figure 19, page 2, item 1) as shown in
Figure 19 and the boiler wiring diagram.
2.  Route  all  low  voltage  wires  through  grommeted
jacket opening to right of low voltage terminal strip,
as shown in Figure 18.
Room thermostat 
(space heating)
1.  For combined space heating/water heating systems,
connect Figure 19, item 2, room thermostat or end
switch (isolated contact only) between terminals 
and .
2.  Install thermostat on inside wall away from influ-
ences  of  drafts,  hot  or  cold  water  pipes,  lighting
fixtures, television, sunrays, or fireplaces.
.  Thermostat anticipator (if applicable):
a.  If connected directly to boiler, set for 0.1 amps.
b.  If connected to relays or other devices, set to match
total  electrical  power  requirements  of  connected
devices. See device manufacturers’ specifications and
thermostat instructions for details.
Outdoor temperature sensor
1.  Outdoor reset operation applies only to combined
space heating/water heating systems.
2.  Connect  outdoor  temperature  sensor  (Figure 19,
item ) between terminals 1 and 2 to enable out-
door  reset  operation  of  the
 Gasboiler.  If
fixed-temperature  operation  is  required,  do  not
install outdoor sensor.
.  Mount sensor on exterior wall, shielded from di-
rect sunlight or flow of heat or cooling from other
sources.
.  Install a summer/winter switch (Figure 19, item )
across terminals 1 and 2 to force fixed-temperature
operation  during  summer  months.  (When  the
switch  is  closed,  boiler  will  attempt  to  maintain
constant temperature.)
.  Route sensor wires through the grommeted hole at
right of the electrical entrance (see Figure 18).
Water heater thermostat
1.  Connect  PLUS  water  heater  aquastat  terminals
“C”  and “1”  to
 Gas  boiler  low  voltage  ter-
minal  strip  between  terminals    and   (Figure 9,
item ).
Additional limits
1.  Connect  additional  limit  controls  and  interlocks
between the terminals shown in Figure 19.
2.  Controls  connected  between  terminals    and  
(see  Figure 19,  item  )  will  cause  a  soft  lockout
(automatic reset). When limit(s) closes, boiler will
resume normal operation.
.  Controls  connected  between  terminals    and  8
(see Figure 19, item ). will cause a hard lockout
(manual  reset).  The  boiler  will  only  restart  after
the Ultra display panel RESET switch is pressed.
Figure 18 
Routing field wiring
Field wiring — 
 Gas boilers only
 
(continued)