4.3.4  D
IMENSIONING THE ALTERNATIVE ENERGY SOURCES
 
In a hybrid system, the alternative energy sources such as the solar generator, wind power and 
small hydropower should, in principle, be dimensioned in such a way as to be able to cover the 
average daily consumption. 
4.4
  Wiring diagrams 
The diagrams shown in the appendix of this document are subsidiary. The applicable local 
installation regulations and standards must be adhered to. 
The elements referred to with an uppercase letter denote the alternate current (AC) part. 
The elements referred to with a lowercase letter denote the direct current (DC) part. 
4.5
  Connecting the battery 
Lead batteries are usually available in 2 V, 6 V or 12 V block types. In the majority of cases, in order 
to obtain an operating voltage that is correct for Xtender usage, several batteries must be connected 
in series or in parallel depending on the circumstances.  
 
 
 
In multi-unit systems, all Xtenders from the same system must be connected according to 
the same battery bank. 
 
The various cabling options are presented in figures 5a-5b (12 V), 5c-5e (24 V) and 6a to 6d (48 V) in 
appendix I of this manual.  
 
4.5.1 
 
M
INIMUM BATTERY CABLE CROSS
-
SECTION 
 
XTH3000-12
 
XTH5000-24
 
XTH6000-48
 
XTH8000-48
 
90 mm
2
 90 
mm
2
 70 
mm
2
 90 
mm
2
 
 
The cable sections recommended above are valid for lengths less than 3 m. beyond this length it is 
strongly recommended to over-section the battery cables. 
The battery cables must also be as short as possible.  
It is always preferable to keep the cable at the negative pole of the battery as short as possible. 
 
4.5.2  C
ONNECTING THE BATTERY 
(X
TENDER SIDE
Insert the conduit glands supplied on the battery cable before tightening the cable clamp. Crimp the 
cable clamps and fasten the conduit gland on the device. Repeat this for the second battery cable. 
Fix the battery cables to the appropriate connections „+ Battery “and „- Battery “. The M8 screws 
must be very well tightened.  
 
4.5.3  DC
 INPUT PROTECTION
 
In order to avoid any further loss and protection 
redundancy, the Xtender does not have an 
internal fuse. A protection device (f) must be 
installed as close as possible to the battery and 
sized as per the table opposite: 
 
 
 
Unit
 
Fuse on the battery side
 
XTH-3000-12 
400 A 
XTH-5000-24 
350 A 
XTH-6000-48 
250 A 
XTH-8000-48 
300 A