Studer Innotec XTH 8000-48 Manual Do Utilizador

Página de 36
STUDER Innotec 
Xtender 
Installation and operating Instructions 
Xtender V1.3 
Page 16 
 
6
  Description and functioning 
The Xtender is a sine wave inverter with a battery charger. It has been developed for use as a stand-
alone installation to supply AC voltage (not connected to the grid) or as a continuous supply. 
6.1
  Circuit diagram 
RJ45
A
C
 IN
N
N
BATTERY
4x2,7M
Ω
Temp.
max 300m
AC
 O
U
T
 
DSP
RJ11
CAN bus
L1
L2
L3
AU
X
IL
L
A
R
Y
C
ON
T
A
C
T
XTH-5000-24
M ultimod e Power Center
10nF
10nF
L
2,2nF
100nF
8p
8p
Bus termination
6p
T
O
Remote 
On/Off
L
DC
AC
Au
x
2
Au
x
1
RCC-02
2,2nF
2,2nF
2,2nF
K1
K2
K3
K4
10
9
14
13
11
12
2
4
7
6
3
16
17
a
b
f
BT
S-
0
1
e
f
t
 
6.2
  Description of the main functions 
6.2.1  I
NVERTER
 
The Xtender is equipped with a high-performance inverter which supplies a perfect and very precise 
sine wave. Any unit designed for the 230 V/50 Hz electrical grid may connect to it without any 
problem, up to the rated power out of your Xtender. The inverter is protected against overloads and 
short-circuits. 
Thanks to the largely over-dimensioned performance level, loads of up to three times greater than 
the Xtender’s rated output can be faultlessly supplied for short periods of use, thus allowing motors 
to be started up without any problem. 
When the Xtender is operating the LED “ON” (43) is glowing. 
When the Xtender is in inverter mode, the LED “AC out” (46) is glowing. If it flashes, the inverter is in 
“load search” mode (see following chapter “Automatic load detection”). 
6.2.2  A
UTOMATIC LOAD DETECTION
 
In order to save battery energy, the Xtender inverter stops and automatically goes into load search 
when the detected load is lower than the sensitivity set by the configuration {1187}. It automatically 
goes back into operation when a power consumer greater than this value demands it. The indicator 
(46) flashes if the inverter is in “load search” mode, which also indicates that the AC voltage is 
present at the output in an intermittent form.  
The detection threshold for the absence of loads can be adjusted according to the configuration